SETPOINTS MENU

Parameter

Parameter 

Default

Value

Parameter

Range and

Increment

a

Notes

MAT SET

53ºF

38 to 70ºF;

in cre ment  by  1

Setpoint de ter mines where the economizer will mod u late the OA damper to main tain the mixed
air  tem per a ture.

LOW T LOCK

32ºF

-45 to 80ºF;

in cre ment  by  1

Setpoint  de ter mines  out door  tem per a ture  when  the  me chan i cal  cool ing  can not  be  turned  on.
Com monly re ferred to as the Com pres sor lockout.

DRYBLB SET

63ºF

48 to 80ºF;

in cre ment  by  1

Setpoint de ter mines where the economizer will as sume out door air tem per a ture is good for free
cool ing; e.g.; at 63ºF unit will economizer at 62ºF and be low and not econ o mize at 64ºF and
above. There is a 2ºF deadband.

ENTH CURVE

ES3

ES1, ES2, ES3,

ES4, or ES5

Does not dis play if a field in stalled Dual Enthalpy kit is con nected. Enthalpy bound ary "curves"
for econ o miz ing us ing sin gle enthalpy com par i son be tween out door air enthalpy and setpoint.

DCV SET

1100 ppm

500 to 2000 ppm

in cre ment  by  100

Dis plays ONLY if field in stalled CO

2

 sen sor is con nected. Setpoint for De mand Con trol Ven ti la -

tion of space. Above the setpoint, the OA damp ers will mod u late open to bring in ad di tional OA
to main tain a space ppm level be low the setpoint.

MIN POS

2.8 V

2 to 10 Vdc

Dis plays ONLY if a CO

2

 sen sor is NOT con nected.

With 2-speed fan units MIN POS L (low speed fan) and MIN POS H (high speed fan) set -
tings are re quired. De fault for MIN POS L is 3.2V and MIN POS H is 2.8V

VENTMAX

2.8 V

2 to 10 Vdc

Dis plays only if a field in stalled CO

2

 sen sor is con nected. Used for Vbz (ven ti la tion max cfm)

setpoint. VENTMAX is the same set ting as MIN POS would be if you did not have the CO

2

 sen -

sor.

100 to 9990 cfm

in cre ment  by  10

If OA, MA, RA and CO

2

 sen sors are con nected and DCV CAL EN ABLE is set to AUTO mode,

the OA damp ers are con trolled by CFM and dis plays from 100 to 9990 cfm.

2 to 10 Vdc

With 2-speed fan units VENTMAX L (low speed fan) and VENTMAX H (high speed fan)
set tings are re quired. De fault for VENTMAX L is 3.2V and VENTMAX H is 2.8V.

VENTMIN

2.25 V

2 to 10 Vdc

Dis plays only if field in stalled CO

2

 sen sor is con nected. Used for Va (ven ti la tion min cfm)

setpoint. This is the ven ti la tion re quire ment for less than max i mum oc cu pancy of the space.

100 to 9990 cfm

in cre ment  by  10

If OA, MA, RA and CO

2

 sen sors are con nected and DCV CAL EN ABLE is set to AUTO mode,

the OA damp ers are con trolled by CFM and dis plays from 100 to 9990 cfm.

2 to 10 Vdc

With 2-speed fan units VENTMIN L (low speed fan) and VENTMIN H (high speed fan) set -
tings are re quired. De fault for VENTMIN L is 2.5V and VENTMIN H is 2.25V.

ERV OAT SP

32ºF

0 to 50ºF;

in cre ment  by  1

Only when AUX1 O = ERV

EXH1 SET

50%

0 to 100%;

increment by 1

Setpoint for OA damper po si tion when ex haust fan 1 is pow ered by the economizer. With
2-speed fan units Exh1 L (low speed fan) and Exh1 H (high speed fan) set tings are re quired.
De fault for Exh1 L is 65% and Exh1 H is 50%.

EXH2 SET

75%

0 to 100%;

increment by 1

Setpoint for OA damper po si tion when ex haust fan 2 is pow ered by the economizer. Only used
when AUX1 O is set to EHX2.
With 2-speed fan units Exh2 L (low speed fan) and Exh2 H (high speed fan) set tings are re -
quired. De fault for Exh2 L is 80% and Exh2 H is 75%.

Содержание Jade XRD-01RDHAM3 Series

Страница 1: ...REQUIRED FOR INSTALLATION 3 8 electric drill with 5 16 socket Waterproof exterior duct sealant Sheet metal tools e g shears PACKAGE CONTENTS XRD 01RDHAM3 economizer with controller actuator and outsid...

Страница 2: ...ng economizer insertion STEP 5 Remove jumper plug and slide economizer into unit return air section SEE FIGURE 2 After the economizer is installed c o n n e c t u n i t E C O N O M I Z E R P L U G t o...

Страница 3: ...STEP 10 Slide PERMANENT FILTERS between OA RAINHOOD LEFT SIDE and OA RAINHOOD RIGHT SIDE back into the 12 OA FILTER RAIL STEP 11 Fasten 11 OA RAINHOOD FRONT FILTER SUPPORT to PANEL TOP LEFT The botto...

Страница 4: ...NOTE The sensor is a white wire that ships strapped to the economizer wire harness The sensor should be secured with the included wire tie to avoid entanglement with the blower and direct contact wit...

Страница 5: ...1 C2 C3 Return Air Enthalpy Sensor ON OFF OFF Outside Air Enthalpy Sensor OFF OFF OFF XRX AR02 Wall Mounted Carbon Dioxide Sensor For installations requiring Demand Control Ventilation DCV based upon...

Страница 6: ...he first item in the currently displayed menu l Use the p and q buttons to scroll to the desired parameter l Press the 8 button Enter to display the value of the currently displayed item l Press the p...

Страница 7: ...midity Displays if not connected short or out of range RA TEMP _ _ _ F 0 to 140 F If field installed Dual Enthalpy sensor is connected displays measured value of return air tem perature Displays F if...

Страница 8: ...lled CO2 sensor is connected Used for Vbz ventilation max cfm setpoint VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sen sor 100 to 9990 cfm increment by 10 If OA MA RA a...

Страница 9: ...2 speed supply fan NOTE 2 speed fan option also needs Heat W1 programmed in AUX 2 In FAN CFM 5000cfm 100 to 15000 cfm increment by 100 This is the airflow capacity of the rooftop unit or air handler T...

Страница 10: ...All other controls e g Y1 O Y2 O EXH1 etc will shut off DCVCAL ENA MAN MAN manual AUTO Displays only if all sensors RA OA MA and CO2 are connected Turns on the DCV auto matic control of the dampers Re...

Страница 11: ...tch settings or is not available if AUX1 O is set to NONE Checkout Tests Use the Checkout menu to test the damper operation and any configured outputs Only items that are configured are shown in the C...

Страница 12: ...temperature and OA humidity readings 3 With power applied to the unit and the C7400S sensor connected change the sensor s 3 position DIP switch in the order shown below without delay between steps fr...

Страница 13: ...its 60 minutes before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational The exception is the MA sensor which will alarm immediately If one...

Страница 14: ...c Default for EXH1 L is 65 and EXH1 H is 50 d After the outside air damper output command DAMPER OUT not ACT POS reaches the power exhaust setpoint the power exhaust output EXH1 is energized after a...

Страница 15: ...ting iii If the mixed air temperature drops below 45 F MA LO SET Freeze Protect Mode Setpoint the DCV input will be overridden and the damper may not open j Ensure proper polarity of the sensor wires...

Страница 16: ...ON VENTMIN Above Setpoint NO OFF OFF OFF ON c OFF OFF VENTMIN to VENTMAX ON OFF OFF ON ON OFF VENTMIN to VENTMAX ON ON OFF ON ON ON VENTMIN to VENTMAX ON OFF ON d ON ON OFF VENTMIN to VENTMAX ON ON O...

Страница 17: ...FF CLOSED ON ON ON d ON ON ON CLOSED YES OFF OFF OFF ON OFF OFF CLOSED ON OFF OFF ON OFF OFF CLOSED to 100 ON ON OFF ON ON OFF b CLOSED to 100 ON OFF ON d ON ON OFF CLOSED ON ON ON d ON ON ON CLOSED A...

Страница 18: ...olet WHT White YEL Yellow COMPONENT CODE Revision Change Date HARNESS ENDS AT PL20 10J1H Mixed Air Sensor C7400S Fresh Air Sensor J2 Power Exhaust Cap MS3110J Damper Actuator 24v PL6 Male Interface Un...

Отзывы: