RRS Jade XRD-01RDHAM3 Series Скачать руководство пользователя страница 4

4

ST-A1230-05

STEP 15:

Provide opening in return air duct to mount the two
barometric relief dampers and hoods 

(SEE FIGURE 4)

.

Locate a convenient distance from unit.

STEP 16:

Using self-drilling screws provided, assemble exhaust air
rain hoods (

„

 EXHAUST AIR RAINHOOD – TOP, 

‡

EXHAUST AIR RAINHOOD - LEFT SIDE,  

ˆ

 EXHAUST

AIR RAINHOOD - RIGHT SIDE,  

ƒ

 SPOTWELD ASSY -

BIRD SCREEN) and install in return air duct. Use sealant
(not provided) as required.

STEP 17:

Either open the BLOWER MOTOR HINGED DOOR or
remove the BLOWER MOTOR ACCESS PANEL 

(SEE

FIGURE 5)

.

STEP 18:

Connect the 



 DISCHARGE AIR SENSOR to wires 51

and 52 located in the blower motor compartment.

NOTE:

The sensor is a white wire that ships strapped to the
economizer wire harness. The sensor should be secured
with the included wire tie to avoid entanglement with the
blower and direct contact with any sheet metal surfaces.

STEP 19:

Either close the BLOWER MOTOR HINGED DOOR or
reinstall the BLOWER MOTOR ACCESS PANEL.

STEP 20:

Upon start-up check the economizer sequence of
operation using the steps provided in these instructions.
After testing unit operation and setting outside air damper
minimum position, secure PANEL – LEFT BOTTOM
SECTION 

(SEE FIGURE 3) 

with remaining screws. 

ˆ

ƒ

„

„

‡

‡

17.790

16.290

18.500

1.500

MIN.

WIRE TIE TO
SECURE SENSOR



FIGURE 4

ST-A1230-07

.000

.000

34.080

RECOMMENDED DUCT OPENING

SUPPLY AIR DUCT

ATTACH TO UNIT

RETURN AIR DUCT

CUT OPENINGS AND 

ATTACH TO UNIT

RELIEF DAMPERS

SLIDE IN DUCT

OPENINGS

FIGURE 5

Содержание Jade XRD-01RDHAM3 Series

Страница 1: ...REQUIRED FOR INSTALLATION 3 8 electric drill with 5 16 socket Waterproof exterior duct sealant Sheet metal tools e g shears PACKAGE CONTENTS XRD 01RDHAM3 economizer with controller actuator and outsid...

Страница 2: ...ng economizer insertion STEP 5 Remove jumper plug and slide economizer into unit return air section SEE FIGURE 2 After the economizer is installed c o n n e c t u n i t E C O N O M I Z E R P L U G t o...

Страница 3: ...STEP 10 Slide PERMANENT FILTERS between OA RAINHOOD LEFT SIDE and OA RAINHOOD RIGHT SIDE back into the 12 OA FILTER RAIL STEP 11 Fasten 11 OA RAINHOOD FRONT FILTER SUPPORT to PANEL TOP LEFT The botto...

Страница 4: ...NOTE The sensor is a white wire that ships strapped to the economizer wire harness The sensor should be secured with the included wire tie to avoid entanglement with the blower and direct contact wit...

Страница 5: ...1 C2 C3 Return Air Enthalpy Sensor ON OFF OFF Outside Air Enthalpy Sensor OFF OFF OFF XRX AR02 Wall Mounted Carbon Dioxide Sensor For installations requiring Demand Control Ventilation DCV based upon...

Страница 6: ...he first item in the currently displayed menu l Use the p and q buttons to scroll to the desired parameter l Press the 8 button Enter to display the value of the currently displayed item l Press the p...

Страница 7: ...midity Displays if not connected short or out of range RA TEMP _ _ _ F 0 to 140 F If field installed Dual Enthalpy sensor is connected displays measured value of return air tem perature Displays F if...

Страница 8: ...lled CO2 sensor is connected Used for Vbz ventilation max cfm setpoint VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sen sor 100 to 9990 cfm increment by 10 If OA MA RA a...

Страница 9: ...2 speed supply fan NOTE 2 speed fan option also needs Heat W1 programmed in AUX 2 In FAN CFM 5000cfm 100 to 15000 cfm increment by 100 This is the airflow capacity of the rooftop unit or air handler T...

Страница 10: ...All other controls e g Y1 O Y2 O EXH1 etc will shut off DCVCAL ENA MAN MAN manual AUTO Displays only if all sensors RA OA MA and CO2 are connected Turns on the DCV auto matic control of the dampers Re...

Страница 11: ...tch settings or is not available if AUX1 O is set to NONE Checkout Tests Use the Checkout menu to test the damper operation and any configured outputs Only items that are configured are shown in the C...

Страница 12: ...temperature and OA humidity readings 3 With power applied to the unit and the C7400S sensor connected change the sensor s 3 position DIP switch in the order shown below without delay between steps fr...

Страница 13: ...its 60 minutes before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational The exception is the MA sensor which will alarm immediately If one...

Страница 14: ...c Default for EXH1 L is 65 and EXH1 H is 50 d After the outside air damper output command DAMPER OUT not ACT POS reaches the power exhaust setpoint the power exhaust output EXH1 is energized after a...

Страница 15: ...ting iii If the mixed air temperature drops below 45 F MA LO SET Freeze Protect Mode Setpoint the DCV input will be overridden and the damper may not open j Ensure proper polarity of the sensor wires...

Страница 16: ...ON VENTMIN Above Setpoint NO OFF OFF OFF ON c OFF OFF VENTMIN to VENTMAX ON OFF OFF ON ON OFF VENTMIN to VENTMAX ON ON OFF ON ON ON VENTMIN to VENTMAX ON OFF ON d ON ON OFF VENTMIN to VENTMAX ON ON O...

Страница 17: ...FF CLOSED ON ON ON d ON ON ON CLOSED YES OFF OFF OFF ON OFF OFF CLOSED ON OFF OFF ON OFF OFF CLOSED to 100 ON ON OFF ON ON OFF b CLOSED to 100 ON OFF ON d ON ON OFF CLOSED ON ON ON d ON ON ON CLOSED A...

Страница 18: ...olet WHT White YEL Yellow COMPONENT CODE Revision Change Date HARNESS ENDS AT PL20 10J1H Mixed Air Sensor C7400S Fresh Air Sensor J2 Power Exhaust Cap MS3110J Damper Actuator 24v PL6 Male Interface Un...

Отзывы: