CHECKOUT MENU

Parameter

Parameter

Default Value

Parameter Range 

and Increment

a

Notes

DAMPER VMIN-HS

n/a

n/a

Po si tions damper to VMIN po si tion

DAMPER VMAX-HS

n/a

n/a

Po si tions damper to VMAX po si tion. 

DAMPER VMAX-LS

With 2-speed fan units the damper will po si tion to VMAX low speed fan.

DAMPER OPEN

n/a

n/a

Po si tions out side air damper to the full open po si tion.

DAMPER CLOSE

n/a

n/a

Po si tions out side air damper to the fully closed po si tion.

CONNECT Y1-O

n/a

n/a

Closes the Y1-O re lay (Y1-O); en er gizes 1st stage com pres sor.

CONNECT Y2-O

n/a

n/a

Closes the Y2-O re lay (Y2-O); en er gizes 2nd stage com pres sor.

CONNECT EXH1

n/a

n/a

Closes the power ex haust fan 1 re lay (EXH1)

CONNECT EXH2

n/a

n/a

En er gizes the EXH2 out put. The EXH2-O can be re placed by:

l

ERV

l

EXH2

l

SYS.

l

AUX1 O

Based on AUX1 O switch set tings or is not avail able if AUX1 O is set to NONE

Check out  Tests

Use the Checkout menu to test the damper operation and any configured outputs. Only items that are configured are
shown in the Checkout menu.

To perform a Checkout test:

1.

Scroll to the desired test in the Checkout menu using the

 

p

 and 

q

 buttons.

2.

Press the

 

8

 

 

button to select the item.

3.

RUN? appears on the display.

4.

Press the

 

8

 

 

button to start the test.

5.

The unit pauses and then displays 

TEST RUNNING

.

6.

Press the button

 

Ó

 

(Menu up) to end the test (e.g. turn off the relay). Test stops automatically after 10 minutes without

a command or mode change, and will resume normal operation.

The checkout tests can all be performed at the time of installation or any time during the operation of the system as a test
that the system is operable.

NOTE: 

Be sure to allow for enough time for compressor startup and shutdown between checkout tests so that you do not

short-cycle the compressors and damage them from extreme short-cycling.

Содержание Jade XRD-01RDHAM3 Series

Страница 1: ...REQUIRED FOR INSTALLATION 3 8 electric drill with 5 16 socket Waterproof exterior duct sealant Sheet metal tools e g shears PACKAGE CONTENTS XRD 01RDHAM3 economizer with controller actuator and outsid...

Страница 2: ...ng economizer insertion STEP 5 Remove jumper plug and slide economizer into unit return air section SEE FIGURE 2 After the economizer is installed c o n n e c t u n i t E C O N O M I Z E R P L U G t o...

Страница 3: ...STEP 10 Slide PERMANENT FILTERS between OA RAINHOOD LEFT SIDE and OA RAINHOOD RIGHT SIDE back into the 12 OA FILTER RAIL STEP 11 Fasten 11 OA RAINHOOD FRONT FILTER SUPPORT to PANEL TOP LEFT The botto...

Страница 4: ...NOTE The sensor is a white wire that ships strapped to the economizer wire harness The sensor should be secured with the included wire tie to avoid entanglement with the blower and direct contact wit...

Страница 5: ...1 C2 C3 Return Air Enthalpy Sensor ON OFF OFF Outside Air Enthalpy Sensor OFF OFF OFF XRX AR02 Wall Mounted Carbon Dioxide Sensor For installations requiring Demand Control Ventilation DCV based upon...

Страница 6: ...he first item in the currently displayed menu l Use the p and q buttons to scroll to the desired parameter l Press the 8 button Enter to display the value of the currently displayed item l Press the p...

Страница 7: ...midity Displays if not connected short or out of range RA TEMP _ _ _ F 0 to 140 F If field installed Dual Enthalpy sensor is connected displays measured value of return air tem perature Displays F if...

Страница 8: ...lled CO2 sensor is connected Used for Vbz ventilation max cfm setpoint VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sen sor 100 to 9990 cfm increment by 10 If OA MA RA a...

Страница 9: ...2 speed supply fan NOTE 2 speed fan option also needs Heat W1 programmed in AUX 2 In FAN CFM 5000cfm 100 to 15000 cfm increment by 100 This is the airflow capacity of the rooftop unit or air handler T...

Страница 10: ...All other controls e g Y1 O Y2 O EXH1 etc will shut off DCVCAL ENA MAN MAN manual AUTO Displays only if all sensors RA OA MA and CO2 are connected Turns on the DCV auto matic control of the dampers Re...

Страница 11: ...tch settings or is not available if AUX1 O is set to NONE Checkout Tests Use the Checkout menu to test the damper operation and any configured outputs Only items that are configured are shown in the C...

Страница 12: ...temperature and OA humidity readings 3 With power applied to the unit and the C7400S sensor connected change the sensor s 3 position DIP switch in the order shown below without delay between steps fr...

Страница 13: ...its 60 minutes before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational The exception is the MA sensor which will alarm immediately If one...

Страница 14: ...c Default for EXH1 L is 65 and EXH1 H is 50 d After the outside air damper output command DAMPER OUT not ACT POS reaches the power exhaust setpoint the power exhaust output EXH1 is energized after a...

Страница 15: ...ting iii If the mixed air temperature drops below 45 F MA LO SET Freeze Protect Mode Setpoint the DCV input will be overridden and the damper may not open j Ensure proper polarity of the sensor wires...

Страница 16: ...ON VENTMIN Above Setpoint NO OFF OFF OFF ON c OFF OFF VENTMIN to VENTMAX ON OFF OFF ON ON OFF VENTMIN to VENTMAX ON ON OFF ON ON ON VENTMIN to VENTMAX ON OFF ON d ON ON OFF VENTMIN to VENTMAX ON ON O...

Страница 17: ...FF CLOSED ON ON ON d ON ON ON CLOSED YES OFF OFF OFF ON OFF OFF CLOSED ON OFF OFF ON OFF OFF CLOSED to 100 ON ON OFF ON ON OFF b CLOSED to 100 ON OFF ON d ON ON OFF CLOSED ON ON ON d ON ON ON CLOSED A...

Страница 18: ...olet WHT White YEL Yellow COMPONENT CODE Revision Change Date HARNESS ENDS AT PL20 10J1H Mixed Air Sensor C7400S Fresh Air Sensor J2 Power Exhaust Cap MS3110J Damper Actuator 24v PL6 Male Interface Un...

Отзывы: