4.

MIN POS

 - Outside Air Damper minimum position

a.

Displays ONLY if a CO

2

 sensor is NOT connected. 

With 2-speed fan units MIN POS L (low speed fan)
and MIN POS H (high speed fan) settings are
required. Default for MIN POS L is 3.2V and MIN
POS H is 2.8V.

b.

Adjust MIN POS to allow the minimum amount of
outdoor air, as required by local codes, to enter the 
building.

c.

Range of adjustment is from 0-100% (2-10V); in
most applications MIN POS is adjusted to allow
10% to 25% outside air to enter the system.

d.

MIN POS can be adjusted at any time.

e.

Whenever the “G” (supply fan) signal is present,
the damper will open to this minimum position
unless the mixed air sensor falls below the MA LO
SET (Freeze Protect Mode Setpoint).

5.

VENTMAX

 - Demand Control Ventilation (DCV)

Maximum Setpoint
a.

Displays only if a CO

2

 sensor is connected.

b.

VENTMAX allows the installer to limit the amount
of outdoor airflow into the building when DCV
overrides the mixed air temperature sensor
setpoint. It is normally equal to the minimum
a m o u n t   o f   o u td o o r   a i r   u n d e r   m a x i m u m
occupancy, as required by local codes, to enter
the building.

c.

VENTMAX can be adjusted at any time.

6.

VENTMIN

 - Demand Control Ventilation (DCV)

Setpoint
a.

Displays only if a CO

2

 sensor is connected.

b.

Is the ventilation requirement for less than

maximum occupancy of the space.

c.

Compatible CO

2

 sensors will have a 2-10Vdc

output for a 0-2000 ppm CO

2

 input. 

d.

DCV modulates the outdoor damper between the
VENTMIN and VENTMAX settings to provide
ventilation based on occupancy. The carbon
dioxide (CO

2

) sensor is used to indirectly monitor

occupancy level.

e.

No cooling signal (e.g.Y1, Y2) is required for DCV
to override the outdoor air damper when
ventilation requires outdoor air.

f.

The controller must receive a “G” (supply fan)
signal to open the damper.

g.

Range of adjustment is from 2 Volts to 10 Volts.

h.

VENTMIN can be adjusted at any time.

I.

The controller compares the CO

2

 sensor input to

VENT MIN to determine the damper minimum
position.
I.

If the actual CO

2

 level is below the setpoint,

then the damper minimum position is
determined by the damper minimum position
(VENTMIN) setting.

ii.

If the actual CO

2

 level rises above the

setpoint, then the damper minimum position is 
overridden proportionally more open up to the
VENTMAX setting.

iii. If the mixed air temperature drops below 45°F

(MA LO SET - Freeze Protect Mode Setpoint), 
the DCV input will be overridden and the
damper may not open.

j.

Ensure proper polarity of the sensor wires when
connecting to the economizer controller. Incorrect
polarity negates the sensor signal.

NOR MAL  OP ER A TION

1.

Fan Only (G)

a.

Damper will go to minimum position (in 90

seconds or less) whenever the “G” (supply fan)
signal is present.

b.

When “G” signal is removed, the outside air
damper closes against blade seals for tight shutoff 
of outside air.

c.

If the mixed air temperature drops below 45°F (MA 
LO SET Setpoint), then the control will override
the minimum position setting and will modulate the 
outside air damper closed.

2.

Call for First Stage of Cooling (Y1)

a.

Economizer Unavailable (warm outdoor air):

Closes the Y1-O relay (Y1-O) which energizes 1st
stage compressor.

b.

Economizer Available (free cooling): The

controller tries to maintain a mixed air temperature 
of 53°F ± 5 (MAT SET Setpoint) by modulating the
outside air damper position.

3.

Call for Second Stage of Cooling (Y2)

a.

Economizer Unavailable (warm outdoor air):

Closes the Y2-O relay (Y2-O) which energizes
2nd stage compressor.

b.

Economizer Available (free cooling): Closes the
Y1-O relay (Y1-O) which energizes 1st stage
compressor. The controller tries to maintain a
mixed air temperature of 53°F ± 5 (MAT SET
Setpoint) by modulating the outside air damper
position. After a time period of 2 hours of
simultaneous economizer operation and first
stage compressor operation, the economizer
closes the Y2-O relay (Y2-O) which energizes 2nd 
stage compressor. 

4.

Call for Heat

a.

Standard Air Conditioner with electric or gas heat.
(W1 & W2)
I.

The Thermostat controls the stages of heating 
directly.

ii.

If the control detects that the supply fan is on
(through its “G” input), then the control will
open the damper to minimum position.

iii. If the mixed air temperature drops below 45°F

(MA LO SET Setpoint), then the control will
override the minimum position setting and will
modulate the outdoor damper closed.

b.

Heat Pump Operation (B)
I.

The “B” signal from the Thermostat allows
operation of the compressors to provide
heating without delay.

ii.

If the control detects that the supply fan is on
(through its “G” input), then the control can
open the damper to minimum position.

iii. If the mixed air temperature drops below 45°F

(MA LO SET Setpoint), then the control will
override the minimum position setting and will
modulate the outdoor damper closed.

Содержание Jade XRD-01RDHAM3 Series

Страница 1: ...REQUIRED FOR INSTALLATION 3 8 electric drill with 5 16 socket Waterproof exterior duct sealant Sheet metal tools e g shears PACKAGE CONTENTS XRD 01RDHAM3 economizer with controller actuator and outsid...

Страница 2: ...ng economizer insertion STEP 5 Remove jumper plug and slide economizer into unit return air section SEE FIGURE 2 After the economizer is installed c o n n e c t u n i t E C O N O M I Z E R P L U G t o...

Страница 3: ...STEP 10 Slide PERMANENT FILTERS between OA RAINHOOD LEFT SIDE and OA RAINHOOD RIGHT SIDE back into the 12 OA FILTER RAIL STEP 11 Fasten 11 OA RAINHOOD FRONT FILTER SUPPORT to PANEL TOP LEFT The botto...

Страница 4: ...NOTE The sensor is a white wire that ships strapped to the economizer wire harness The sensor should be secured with the included wire tie to avoid entanglement with the blower and direct contact wit...

Страница 5: ...1 C2 C3 Return Air Enthalpy Sensor ON OFF OFF Outside Air Enthalpy Sensor OFF OFF OFF XRX AR02 Wall Mounted Carbon Dioxide Sensor For installations requiring Demand Control Ventilation DCV based upon...

Страница 6: ...he first item in the currently displayed menu l Use the p and q buttons to scroll to the desired parameter l Press the 8 button Enter to display the value of the currently displayed item l Press the p...

Страница 7: ...midity Displays if not connected short or out of range RA TEMP _ _ _ F 0 to 140 F If field installed Dual Enthalpy sensor is connected displays measured value of return air tem perature Displays F if...

Страница 8: ...lled CO2 sensor is connected Used for Vbz ventilation max cfm setpoint VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sen sor 100 to 9990 cfm increment by 10 If OA MA RA a...

Страница 9: ...2 speed supply fan NOTE 2 speed fan option also needs Heat W1 programmed in AUX 2 In FAN CFM 5000cfm 100 to 15000 cfm increment by 100 This is the airflow capacity of the rooftop unit or air handler T...

Страница 10: ...All other controls e g Y1 O Y2 O EXH1 etc will shut off DCVCAL ENA MAN MAN manual AUTO Displays only if all sensors RA OA MA and CO2 are connected Turns on the DCV auto matic control of the dampers Re...

Страница 11: ...tch settings or is not available if AUX1 O is set to NONE Checkout Tests Use the Checkout menu to test the damper operation and any configured outputs Only items that are configured are shown in the C...

Страница 12: ...temperature and OA humidity readings 3 With power applied to the unit and the C7400S sensor connected change the sensor s 3 position DIP switch in the order shown below without delay between steps fr...

Страница 13: ...its 60 minutes before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational The exception is the MA sensor which will alarm immediately If one...

Страница 14: ...c Default for EXH1 L is 65 and EXH1 H is 50 d After the outside air damper output command DAMPER OUT not ACT POS reaches the power exhaust setpoint the power exhaust output EXH1 is energized after a...

Страница 15: ...ting iii If the mixed air temperature drops below 45 F MA LO SET Freeze Protect Mode Setpoint the DCV input will be overridden and the damper may not open j Ensure proper polarity of the sensor wires...

Страница 16: ...ON VENTMIN Above Setpoint NO OFF OFF OFF ON c OFF OFF VENTMIN to VENTMAX ON OFF OFF ON ON OFF VENTMIN to VENTMAX ON ON OFF ON ON ON VENTMIN to VENTMAX ON OFF ON d ON ON OFF VENTMIN to VENTMAX ON ON O...

Страница 17: ...FF CLOSED ON ON ON d ON ON ON CLOSED YES OFF OFF OFF ON OFF OFF CLOSED ON OFF OFF ON OFF OFF CLOSED to 100 ON ON OFF ON ON OFF b CLOSED to 100 ON OFF ON d ON ON OFF CLOSED ON ON ON d ON ON ON CLOSED A...

Страница 18: ...olet WHT White YEL Yellow COMPONENT CODE Revision Change Date HARNESS ENDS AT PL20 10J1H Mixed Air Sensor C7400S Fresh Air Sensor J2 Power Exhaust Cap MS3110J Damper Actuator 24v PL6 Male Interface Un...

Отзывы: