RRS Jade XRD-01RDHAM3 Series Скачать руководство пользователя страница 7

7

Pa ram e ter

Pa ram e ter

De fault

Value

Pa ram e ter

Range and

In cre ment

a

Notes

ECON AVAIL

NO

YES/NO

YES = econ o miz ing avail able; the sys tem can use Out door Air for free cool ing when re quired.

ECON O MIZ ING

NO

YES/NO

YES = Out door Air be ing used for 1st stage cool ing.

OC CU PIED

NO

YES/NO

YES =  24 Vac OCC sig nal re ceived from space ther mo stat in put. 
 NO = 0 Vac on ter mi nal OCC. 

HEAT PUMP

COOL

COOL/HEAT Dis plays COOL or HEAT when SYS TEM is set to heat pump (nonconventional)

COOL Y1-IN

OFF

ON/OFF

Y1-I sig nal from space ther mo stat in put for cool ing stage 1 or heat pump heat ing stage 1.
ON = 24 Vac on ter mi nal Y1-I
OFF = 0 Vac on ter mi nal Y1-I

COOL Y1-OUT

OFF

ON/OFF

Cool Stage 1 Re lay Out put to stage 1 me chan i cal cool ing (Y1-OUT ter mi nal).

COOL Y2-IN

OFF

ON/OFF

Y2-I sig nal from space ther mo stat in put for sec ond stage cool ing or heat pump heat ing stage 2.
ON = 24 Vac on ter mi nal Y2-I
OFF = 0 Vac on ter mi nal Y2-I

COOL Y2-OUT

OFF

ON/OFF

Cool Stage 2 Re lay Out put to me chan i cal cool ing (Y2-OUT ter mi nal).

MA TEMP

_ _._ºF

-40 to 150ºF

Dis plays value of mea sured mixed air from MAT sen sor. 
Dis plays -.- if not con nected, short, or out-of-range.

DA TEMP

_ _._ºF

-40 to 150ºF

Dis plays when Dis charge Air Sylk Bus sen sor is con nected and dis plays mea sured dis charge
air tem per a ture. Dis plays -.-°F if sen sor sends in valid value, if not con nected, short or
out-of-range.

OA TEMP

_ _._ ºF

-40 to 140ºF

Dis plays mea sured value of out door air tem per a ture. Dis plays -°F if sen sor sends in valid value,
if not con nected, short or out-of-range.

OA HUM

_ _%

0 to 100%

Dis plays mea sured value of out door hu mid ity. Dis plays -% if not con nected, short, or
out-of-range.

RA TEMP

_ _._ºF

0 to 140ºF

If field in stalled Dual Enthalpy sen sor is con nected, dis plays mea sured value of re turn air tem -
per a ture. Dis plays -°F if sen sor sends in valid value, if not con nected, short or out-of-range. 

RA HUM

_ _%

0 to 100%

If field in stalled Dual Enthalpy sen sor is con nected, dis plays mea sured value of re turn air hu -
mid ity. Dis plays -% if sen sor sends in valid value, if not con nected, short or out-of-range.

IN CO

2

_ _ _ ppm

"0 to 2000

(3500) ppm"

If field in stalled CO

2

 sen sor is con nected, dis plays value of mea sured CO

2

. In valid if not con -

nected, short or out-of-range. May be ad justed in Ad vanced menu by Zero off set and Span.

DCV STA TUS

n/a

n/a

If field in stalled CO

2

 sen sor is con nected, dis plays ON if above setpoint and OFF if be low

setpoint.

DAMPER OUT

_ _%

0 to 100%

Dis plays out put po si tion to the damper ac tu a tor. When used with Honeywell com mu ni cat ing ac -
tu a tor the damper out is in XX.X%

ACT POS.

n/a

0 to 100%

Dis plays  ac tual  po si tion  of  ac tu a tor.

ACT COUNT

n/a

1 to 65,535

Dis plays num ber of times ac tu a tor has cy cled. 1 Cy cle equals 180° of move ment in any di rec -
tion.

AC TU A TOR

n/a

OK/Alarm

Dis plays Er ror on ALARM MENU if volt age or torque is be low ac tu a tor range.

EXH1 OUT

OFF

ON/OFF

Out put of EXH1 ter mi nal. - ON = re lay closed; OFF = re lay open.

EXH2 OUT

OFF

ON/OFF

Out put of AUX1 O ter mi nal; dis plays only if AUX1 O = EXH2

ERV

OFF

ON/OFF

Out put of AUX1 O ter mi nal; dis plays only if AUX1 O = ERV

"MECH COOL ON
HEAT  STGS ON"

0

0, 1, or 2

Dis plays stage of me chan i cal cool ing that is ac tive. Dis plays the stage of heat pump heat ing
that is ac tive.

FAN SPEED

n/a

LOW/HIGH

Dis plays speed of fan on a 2-speed fan unit

W (HEAT IN)

n/a

ON/OFF

Dis plays sta tus of heat on a 2-speed fan unit.

STATUS MENU

Содержание Jade XRD-01RDHAM3 Series

Страница 1: ...REQUIRED FOR INSTALLATION 3 8 electric drill with 5 16 socket Waterproof exterior duct sealant Sheet metal tools e g shears PACKAGE CONTENTS XRD 01RDHAM3 economizer with controller actuator and outsid...

Страница 2: ...ng economizer insertion STEP 5 Remove jumper plug and slide economizer into unit return air section SEE FIGURE 2 After the economizer is installed c o n n e c t u n i t E C O N O M I Z E R P L U G t o...

Страница 3: ...STEP 10 Slide PERMANENT FILTERS between OA RAINHOOD LEFT SIDE and OA RAINHOOD RIGHT SIDE back into the 12 OA FILTER RAIL STEP 11 Fasten 11 OA RAINHOOD FRONT FILTER SUPPORT to PANEL TOP LEFT The botto...

Страница 4: ...NOTE The sensor is a white wire that ships strapped to the economizer wire harness The sensor should be secured with the included wire tie to avoid entanglement with the blower and direct contact wit...

Страница 5: ...1 C2 C3 Return Air Enthalpy Sensor ON OFF OFF Outside Air Enthalpy Sensor OFF OFF OFF XRX AR02 Wall Mounted Carbon Dioxide Sensor For installations requiring Demand Control Ventilation DCV based upon...

Страница 6: ...he first item in the currently displayed menu l Use the p and q buttons to scroll to the desired parameter l Press the 8 button Enter to display the value of the currently displayed item l Press the p...

Страница 7: ...midity Displays if not connected short or out of range RA TEMP _ _ _ F 0 to 140 F If field installed Dual Enthalpy sensor is connected displays measured value of return air tem perature Displays F if...

Страница 8: ...lled CO2 sensor is connected Used for Vbz ventilation max cfm setpoint VENTMAX is the same setting as MIN POS would be if you did not have the CO2 sen sor 100 to 9990 cfm increment by 10 If OA MA RA a...

Страница 9: ...2 speed supply fan NOTE 2 speed fan option also needs Heat W1 programmed in AUX 2 In FAN CFM 5000cfm 100 to 15000 cfm increment by 100 This is the airflow capacity of the rooftop unit or air handler T...

Страница 10: ...All other controls e g Y1 O Y2 O EXH1 etc will shut off DCVCAL ENA MAN MAN manual AUTO Displays only if all sensors RA OA MA and CO2 are connected Turns on the DCV auto matic control of the dampers Re...

Страница 11: ...tch settings or is not available if AUX1 O is set to NONE Checkout Tests Use the Checkout menu to test the damper operation and any configured outputs Only items that are configured are shown in the C...

Страница 12: ...temperature and OA humidity readings 3 With power applied to the unit and the C7400S sensor connected change the sensor s 3 position DIP switch in the order shown below without delay between steps fr...

Страница 13: ...its 60 minutes before checking for alarms This allows time for all the configured devices e g sensors actuator to become operational The exception is the MA sensor which will alarm immediately If one...

Страница 14: ...c Default for EXH1 L is 65 and EXH1 H is 50 d After the outside air damper output command DAMPER OUT not ACT POS reaches the power exhaust setpoint the power exhaust output EXH1 is energized after a...

Страница 15: ...ting iii If the mixed air temperature drops below 45 F MA LO SET Freeze Protect Mode Setpoint the DCV input will be overridden and the damper may not open j Ensure proper polarity of the sensor wires...

Страница 16: ...ON VENTMIN Above Setpoint NO OFF OFF OFF ON c OFF OFF VENTMIN to VENTMAX ON OFF OFF ON ON OFF VENTMIN to VENTMAX ON ON OFF ON ON ON VENTMIN to VENTMAX ON OFF ON d ON ON OFF VENTMIN to VENTMAX ON ON O...