Factory settings
DIP switch settings
1 = ON
Storage operation in "CLOSE" direction.
Press ventilation button 1 x shortly > the drives will close to their final position.
1 = OFF
Key operation in "CLOSE" direction.
The drives will close only as long as the ventilation button is pressed.
2 = ON
Storage operation in "OPEN" direction.
Press ventilation button 1 x shortly > the drives will open to their final position.
2 = OFF
Key operation in "OPEN" direction.
The drives will open only as long as the ventilation button is pressed.
3 = ON
Line fault = alarm.
In case of a line fault the control panel will be switched to alarm and the smoke vent opens
(e.g. at an interrupted button line or missing terminal resistor).
4 = ON
Group fault on alarm.
In case of a group fault the control panel will be switched to alarm and the smoke vent opens
(e.g. in case of an interrupted drive line).
5 = ON
OPEN-running time limitation in ventilation operation (Only if DIP switch 2 = ON).
If the vent button is actuated in direction OPEN, the drives open for 30 s (factory-set).
This running time can be edited by PDA servicetool.
6 = ON
Ventilation time limitation (Only if DIP switch 1 = ON).
The drives will automatically close again after the time set (factory-set 10 min).
This time can be edited by the PDA servicetool.
7 = ON
Power failure "CLOSE" (Only if DIP switch 1 = ON).
In case of power failure the drives will close.
8 = ON
Integrated ventilation buttons are activitated.
8 = OFF
Integrated ventilation buttons are deactivitated.
The following functions are (de-) activatable with the PDA-Service Tool:
-
OPEN running time retriggering (factory-set: deactivated)
-
Group CLOSE in case of alarm (factory-set: deactivated)
-
Two smoke detectors dependency (factory-set: deactivated)
-
Smoke detector alarm remote reset (factory-set: deactivated)
-
Lamp test
-
Alarm re-clocking (factory-set: activated)
Hint: In case of alarm the smoke vent is triggered with an OPEN pulse every 2 minutes for a
duration of 30 minutes according to VdS 2581. For this, the drive must be protected against
blockage according to VdS 2580 par. 4.7. . All Roto drives meet this precondition.
-
The signalling relay features the following signals:
pre-alarm, terminated alarm, delayed alarm, general fault, battery fault, line fault, group fault,
power failure, earth fault, passing on of "central CLOSE", "Reset Alarm" as pulse,
group closed longer = x s
(factory-set: signalling relais 1="alarm" signalling relais 2 = "general fault")
Power
230 VAC
Battery
Detector Line
Drive
Group
Module
Connector
X2
OFF
Service
X1
0
Reset
/
I
S1
8
1
ON
ZEL RWA STZ 4503-T
English
99.824.61 1.2/06/11
27/84
Содержание ZEL RWA STZ 4503-T
Страница 1: ...ZEL RWA STZ 4503 T RWA Zentrale S 3 SHEV control panel Centrale DENFC RWA centrale p 23 p 43 p 63 ...
Страница 2: ......
Страница 83: ......
Страница 84: ...99 824 61 1 2 06 11 ...