Informations for starting
Carry out following sight and performance checks for switching-on the smoke and heat vent control panel.
All cables
connected?
Factory-set?
(DIP switch)
10k
resistor
Ω
in smoke vent button
End module 2x47k
in junction box?
Ω
Connect mains.
Mains control
lightens?
Connect
battery lines. Control
lightens?
Smoke
vent flap opens and
closes?
All necessary moving loads connected?
Smoke vent components are line-monitored.
A malfunction is connected as alarm in delivery condition of
control panel. The smoke vent opens self-acting and can be
reset under special conditions only.
yes
yes
yes
yes
yes
yes
yes
Performance check alarm/reset and ventilation
yes
Partial or incomplete connection of
components can cause malfunction.
Check following connections: mains 230V,
drives, smoke vent buttons, when necessary
fire detectors and vent buttons. See wiring an
connection plans pages 34-36.
Delivery condition of DIP switch
see page 21.
Resistor must be cramped in electric last
button on terminal 3/8 (RT 45).
See connection plans pages 34-35.
Resistor must be cramped in last or only fire
detector on terminal 2 and 4
(type FO/FT).
Resistor remains in control panel between
terminal RM 1 and 2, when no fire detector is
connected.
See connection plan page 36.
10k
resistor
in fire detector
Ω
yes
End module on last or only drive in junction
box on wire 5 orange, 6 black, 7 black.
See connection plan page 34.
Check line safety fuse in distribution box and
fuse mains in control panel.
Mains still not available or line switch
on " " or one of fuses faulty.
0
Possibly change poles in drive.
no
no
no
no
no
no
no
no
ZEL RWA STZ 4503-T
English
99.824.61 1.2/06/11
37/84