8 Configuration
Installation and operation manual
21
RHYKOMB33AA
ROTEX HPU hybrid gas boiler module
4P353068-1 – 2013.07
Parameters on the gas boiler
Parameter
Setting
Range
Default
settings
Description
Service code
—
—
To access the installer settings, enter
the service code (=15)
Installation type
0~3
0
▪
0=Combi
▪
1=Heating only + external domestic
hot water tank
▪
2=Domestic hot water only (no
heating system required)
▪
3=Heating only
It is recommended not to modify this
setting.
Space heating pump continuous
0~3
0
▪
0=Post purge period only
▪
1=Pump continuously active
▪
2=Pump continuously active with
MIT switch
▪
3=Pump on with external switch
This setting has no effect.
Maximum space heating power set
~85%
70%
Maximum power in heating. This is a
percentage of the maximum set in
parameter . We strongly recommend
not modifying this setting.
Maximum domestic hot water power
set
~100%
100%
Maximum power in instant domestic
hot water. This is a percentage of the
maximum set in parameter . We
strongly recommend not modifying this
setting.
Minimum supply temperature of the
heat curve
10°C~25°C
15°C
Do NOT modify this setting on the
boiler. Use the user interface instead.
.
Maximum supply temperature of the
heat curve
30°C~90°C
90°C
Do NOT modify this setting on the
boiler. Use the user interface instead.
Minimum outside temperature of the
heat curve
–9°C~10°C
–7°C
Do NOT modify this setting on the
boiler. Use the user interface instead.
Maximum outside temperature of the
heat curve
15°C~30°C
25°C
Do NOT modify this setting on the
boiler. Use the user interface instead.
Space heating pump post purge period 0~15 min
1 min
Changing this setting has no effect on
the operation of the unit.
Space heating pump post purge period
after domestic hot water operation
0~15 min
1 min
Changing this setting has no effect on
the operation of the unit.
Position 3-way valve or electric valve
0~3
0
▪
0=Powered during space heating
▪
1=Powered during domestic hot
water
▪
2=Powered during every heat
demand (space heating, domestic
hot water, eco/comfort)
▪
3=Zone regulation
Booster
0~1
0
Changing this setting has no effect on
the operation of the unit.
Step modulation
0~1
1
▪
0=OFF during space heating
operation
▪
1=ON during space heating
operation
It is recommended not to modify this
setting.
Minimal space heating rpm
23%~50%
23%
Adjustment range 23~50% (40=
propane).
It is recommended not to modify this
setting in case of natural gas.