8 Configuration
Installation and operation manual
22
RHYKOMB33AA
ROTEX HPU hybrid gas boiler module
4P353068-1 – 2013.07
Parameter
Setting
Range
Default
settings
Description
Minimal domestic hot water rpm
23%~50%
23%
Adjustment range 23~50% (40=
propane).
It is recommended not to modify this
setting in case of natural gas.
Minimal supply temperature during OT
demand. (OpenTherm thermostat)
10°C~16°C
40°C
Changing this setting has no effect on
the operation of the unit.
.
OT response
0~2
1
Changing this setting has no effect on
the operation of the unit.
Start rpm space heating
50%~99%
50%
This is the fan rpm before heating
ignition. It is recommended not to
modify this setting.
.
Start rpm domestic hot water
50%~99%
50%
This is the fan rpm before instant
domestic hot water ignition. It is
recommended not to modify this
setting.
Maximum fan rpm
45~50
48
Use this parameter to set the maximum
fan rpm. It is recommended not to
modify this setting.
Set point space heating (flow
temperature) during heating external
domestic hot water tank
60°C~90°C
85°C
Do NOT modify this setting on the
boiler. Use the user interface instead.
.
Comfort temperature
0°C / 40°C~65°C
0°C
Temperature used for eco/comfort
function.
.
Waiting time after a space heating
demand from a thermostat.
0 min~15 min
0 min
Changing this setting has no effect on
the operation of the unit.
Waiting time after a domestic hot water
demand before a space heating
demand is answered.
0 min~15 min
0 min
Amount of time the boiler waits before
answering a space heating demand
after a domestic hot water demand.
.
Number of eco days.
1~10
3
Number of eco days.
Anti-cycling period during space
heating operation
0 min~15 min
5 min
Minimal switch-off time in space
heating operation. It is recommended
not to modify this setting.
Maximum space heating power setting
The maximum space heating power setting ( ) is factory set to 70%.
If more or less power is required, you can change the fan rpm. The
table below shows the relationship between the fan rpm and the
appliance power. It is strongly recommended NOT to modify this
setting.
Desired power (kW)
Setting on service display (%
of max. rpm)
26.2
83
25.3
80
22.0
70
19.0
60
15.9
50
12.7
40
9.6
30
7.0
25
Note that for the gas boiler the power during burning is increased
slowly and is reduced as soon as the supply temperature is reached.
Frost protection function
The boiler is equipped with an internal frost protection function that
automatically operates when necessary, even if the boiler is turned
off. If the heat exchanger temperature drops too low, the burner will
switch on until the temperature is sufficiently high again. When frost
protection is active, is displayed on the service display.
To change to a different type of gas
If a different type of gas is connected to the appliance than that for
which the appliance has been set by the manufacturer, the gas
metering MUST be replaced. Conversion sets for other types of gas
are available to order. See
"5.2.1 List of options for gas boiler" on
page 8
.
1
Switch the boiler off and isolate the boiler from the mains
power.
2
Close the gas tap.
3
Remove the front panel from the appliance.
4
Unscrew the coupling (a) above the gas valve and twist the gas
mixing tube towards the rear (b).
5
Replace the O-ring (c) and the gas restriction (d) with the rings
from the conversion set.
6
Reassemble in reverse sequence.
7
Open the gas tap.
8
Check the gas connections before the gas valve for
gastightness.
9
Switch on the mains power.
10
Check the gas connections after the gas valve for gastightness
(during operation).
11
Now check the setting of the CO
2
percentage at high setting (
in display) and low setting ( in display).
12
Put a sticker indicating the new gas type on the bottom of the
gas boiler, next to the nameplate.
13
Put a sticker indicating the new gas type next to the gas valve,
over the existing one.
14
Put the front panel back in its place.