40
ROTEX GCU compact -
7
x
Gas burner
7.3.1 Setting values
7.3.2 Establishing access to the burner
Ɣ
Remove the sound insulation hood (see chapter 4.4.3).
Ɣ
Remove the upper burner trim (see chapter 4.9.3).
7.3.3 Checking and setting the burner
The gas burner is factory-set to the gas type "Natural gas". The
stipulated gas inlet pressure can be found in tab. 12-5.
The RoCon BF control cab be used to set up the GCU compact
to the function [Emission Measurement] under [Full Load] and
[Base Load]. The flue gas values are inspected with a flue gas
analysis device.
Auxiliary resources
–
Flue gas analysis device.
–
Pressure meter for measuring gas pressure.
Checking and setting
Observe the sequence!
1. Check whether the burner is pre-set to the correct gas type
and the correct gas inlet pressure (see also section 4.9.4).
2. Turn the screw in the gas inlet pressure measuring
connection (fig. 4-32, item 3.3) anticlockwise by half a turn
and push up the measuring hose of the pressure meter.
3. Open the gas stopcock.
4. Measure the gas inlet pressure (idle pressure) and compare
it to the target value (see tab. 12-5). Leave the measuring
instrument connected.
Î
If the gas inlet pressure (resting pressure) is outside the
set value range: Inform your gas supply company or
check the pressure regulator (for liquid gas).
5. Open the heating valves.
6. Switch on ROTEX GCU compact with main switch.
7. Start the [Emission Measurement] on the RoCon BF Control
of the GCU compact and select the setting
[Full Load]
,
but
do not confirm
.
Type
GCU compact 315 / 515 (BIV)
Gas type (test
gas)**
Burner load
in kW
at "Full Load"
O
2
-content
in %
CO
2
-content
in %
Set
+
-
Set
+
-
Natural gas E/H
(G20)
15.7
4.6
0.6
0,2
9.2
0.1
0.3
Natural gas LL/L
(G25)
9.0
0.1
0.3
Propane* (G31)
10.7
0.3
0.5
*
Liquid gas setting
**
Compare with the information on the yellow sticker attached to the burner
housing
Tab. 7-3 Set exhaust setting values for GCU compact 315 and GCU
compact 515 for various gas types
Type
GCU compact 324/ 524 (BIV)
Gas type
(Prüfgas)**
Burner load
in kW
at "Full Load"
O
2
-content
in %
CO
2
-content
in %
Set
+
-
Set
+
-
Natural gas E/H
(G20)
25.3
4.3
0.6
0.2
9.3
0.1
0.3
Natural gas LL/L
(G25)
9.2
0.1
0.3
Propane* (G31)
11.0
0.3
0.5
*
Liquid gas setting
**
Compare with the information on the yellow sticker attached to the burner
housing
Tab. 7-4 Set exhaust setting values for GCU compact 324 and GCU
compact 524 for various gas types
Type
GCU compact 533 (BIV)
Gas type
(Prüfgas)**
Burner load
in kW
at "Full Load"
O
2
-content
in %
CO
2
-content
in %
Set
+
-
Set
+
-
Natural gas E/H
(G20)
32.5
4.0
0.6
0.2
9.5
0.1
0.3
Natural gas LL/L
(G25)
9.3
0.1
0.3
Propane* (G31)
30.0
11.1
0.3
0.5
*
Liquid gas setting
**
Compare with the information on the yellow sticker attached to the burner
housing
Tab. 7-5 Set exhaust setting values for GCU compact 533 for various
gas types
Type
GCU compact 3xx / 5xx (BIV)
Gas type
(Prüfgas)**
Burner load in
kW
at "Base Load"
O
2
-content
in %
CO
2
-content
in %
Set
+
-
Set
+
-
Natural gas E/H
(G20)
6.5
4.4
0.9
0.4
9.3
0.2
0.6
Natural gas LL/L
(G25)
9.1
0.2
0.6
Propane* (G31)
10.8
0.3
0.6
*
Liquid gas setting
**
Compare with the information on the yellow sticker attached to the burner
housing
Tab. 7-6 Set exhaust setting values with "Base Load" for all GCU
compact types for different gas types
If the burner does not start, even with the power and
gas supply properly connected and with the flue gas
path free, the cause for this fault must be found and rec-
tified (see chapter 7.3.4).