APPENDIX FOR REFRIGERANT R290/R32
SPECIFIC INFORMATION REGARDING APPLIANCES WITH R290 / R32
REFRIGERANT GAS.
• Thoroughly read all of the warnings.
• When defrosting and cleaning the appliance, do not use any tools other than those recommended by the
manufacturing company.
• The appliance must be placed in an area with- out any continuously sources of ignition (for example:
open flames, gas or electrical appliances in operation).
• Do not puncture and do not burn.
• This appliance contains Y g (see rating label back of unit) of R290 / R32 refrigerant gas.
• R290 / R32 is a refrigerant gas that complies with the European directives on the environment. Do not
puncture any part of the refrigerant circuit. Be aware the refrigerants may not contain an odour.
• If the appliance is installed, operated or stored in a nonventilated area, the room must be designed to
prevent to the accumulation of refrigerant leaks resulting in a risk of fire or explosion due to ignition of
the refrigerant caused by electric heaters, stoves, or other sources of ignition.
• The appliance must be stored in such a way as to prevent mechanical failure.
• Individuals who operate or work on the refrigerant circuit must have the appropriate certification issued
by an accredited organization that ensures competence in handling refrigerants according to a specific
evaluation recognized by associations in the industry.
• Repairs must be performed based on the recommendation from the manufacturing company.
Maintenance and repairs that require the assistance of other qualified personnel must be per- formed under
the supervision of an individual specified in the use of flammable refrigerants.
Appliances shall be installed,operated and stored in a room with a floor area larger than 4 m2. The appliance
shall be stored in a well-ventilated area where the room size corresponds to the room area as specified for
operation.
INSTRUKCJE NAPRAWY URZĄDZEŃ ZAWIERAJĄCYCH R290 / R32
1. GENERAL INSTRUCTIONS
This instruction manual is intended for use by individuals possessing adequate backgrounds of electrical,
electronic, refrigerant and mechanical experience.
1.1. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary to ensure
that the risk of ignition is minimised. For repair to the refrigerating system, the following precautions shall be
complied with prior to conducting work on the system.
1.2. Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or vapour
being present while the work is being performed.
1.3.General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being
carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned off.
Содержание V26V
Страница 1: ...Versu V26V V35V V50V Instrukcja obs ugi PL...
Страница 30: ...Data wykonania Uwagi serwisu Piecz tka serwisu Podpis 1 2 3 4 5 6 7 8 9 10 REJESTR NAPRAW...
Страница 31: ...NOTATKI...
Страница 32: ...www rotenso pl email info rotenso pl Piecz Instalatora...
Страница 81: ...Lp Data wykonania Uwagi serwisu Piecz tka serwisu Podpis 1 2 3 4 5 6 7 8 9 10 REJESTR NAPRAW...
Страница 123: ...NOTES...
Страница 124: ...email info rotenso com www rotenso com INSTALLER STAMP...
Страница 125: ...Versu V26V V35V V50V Instrukcja obs ugi PL...
Страница 154: ...Data wykonania Uwagi serwisu Piecz tka serwisu Podpis 1 2 3 4 5 6 7 8 9 10 REJESTR NAPRAW...
Страница 155: ...NOTATKI...
Страница 156: ...www rotenso pl email info rotenso pl Piecz Instalatora...