Rosemount 8712
Additional command options may appear that are reserved and do not apply
to the Rosemount 8712.
Burst Option
Burst option enables you to select the variables to broadcast over the
transmitter burst. Choose one of the following options:
•
PV–Selects the process variable for broadcast over the transmitter
burst.
•
Percent Range/Current–Selects the process variable as percent of
range and analog output variables for broadcast over the transmitter
burst.
•
Process vars/crnt–Selects the process variables and analog output
variables for broadcast over the transmitter burst.
•
Dynamic Vars–Burst all dynamic variables in the transmitter.
LOI Configuration
The LOI (local operator interface) configuration contains functionality to
configure the LOI outputs of the transmitter.
Flowrate Display
This allows you to configure the items that the LOI will display when at the
flowrate screen. There are five options available:
•
Flow rate and % Span
•
% Span and Net Total
•
Flowrate and Net Total
•
% Span and Gross Total
•
Flowrate and Gross Total
Totalizer Display
This allows you to configure the items that the LOI will display when in the
totalizer screen. There are two options available:
•
Forward Total and Reverse Total
•
Net Total and Gross Total
Signal Processing
The 8712 contains several advanced functions that can be used to stabilize
erratic outputs caused by process noise. The signal processing menu
contains this functionality.
Operating Mode
The Operating Mode should be used only when the signal is noisy and gives
an unstable output. Filter mode automatically uses 37 Hz coil drive mode and
activates signal processing at the factory set default values. When using filter
mode, perform an auto zero with no flow and a full sensor. Either of the
parameters, coil drive mode or signal processing, may still be changed
individually. Turning Signal Processing off or changing the coil drive frequency
to 5 Hz will automatically change the Operating Mode from filter mode to
normal mode.
Field Comm.
1, 4, 2, 7, 6
Field Comm.
1, 4, 3
Field Comm.
1, 4, 3, 2
Field Comm.
1, 4, 3, 3
Field Comm.
1, 4, 4
LOI Key
AUX. FUNCTION
Field Comm.
1, 4, 4, 1
Содержание 8712
Страница 2: ......
Страница 4: ......
Страница 26: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 2 16 ...
Страница 84: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 4 46 ...
Страница 102: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 5 18 ...
Страница 114: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 6 12 ...
Страница 131: ...Reference Manual 00809 0100 4664 Rev BA January 2010 B 7 Rosemount 8712 Figure B 1 CSA Installation ...
Страница 132: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 B 8 Figure B 2 Factory Mutual Hazardous Locations ...
Страница 154: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 D 6 ...
Страница 194: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 E 40 ...
Страница 208: ...Reference Manual 00809 0100 4664 Rev BA January 2010 Rosemount 8712 F 14 ...
Страница 211: ......