Reference Manual
00809-0100-4022, Rev AA
July 2002
Model 4600
5-2
Table 5-1. Model 4600
troubleshooting table
Symptom
Corrective Actions
Transmitter milliamp reading is zero
Verify power is applied to signal terminals
Check power wires for reversed polarity
Verify terminal voltage is 11.25 to 42.4 V dc
Transmitter Not Communicating with
HART Communicator
Verify the output is between 4 and 20 mA or saturation levels
Verify clean DC Power to transmitter (Max AC noise 0.2 volts peak to peak)
Check loop resistance, 250
Ω
minimum (PS voltage -transmitter voltage/loop current)
Check if unit is addressed properly
Transmitter milliamp reading is low or high
Verify applied pressure
Verify 4 and 20 mA range points
Verify output is not in alarm condition
Verify if 4 – 20 mA output trim is required
Transmitter will not respond to changes in
applied pressure
Check test equipment
Check impulse piping or manifold for blockage
Verify applied pressure is between the 4 and 20 mA set points
Verify output is not in alarm condition
Verify transmitter is not in Loop Test mode
Digital Pressure Variable reading is low or high
Check test equipment (verify accuracy)
Check impulse piping for blockage or low fill in wet leg
Verify transmitter is calibrated properly
Verify pressure calculations for application
Digital Pressure Variable reading is erratic
Check application for faulty equipment in pressure line
Verify transmitter is not reacting directly to equipment turning on/off
Verify damping is set properly for application
Milliamp reading is erratic
Verify power source to transmitter has adequate voltage and current
Check for external electrical interference
Verify transmitter is properly grounded
Verify shield for twisted pair is only grounded at one end
HART message reading:
“Brown-out condition detected.”
Verify power source to transmitter has adequate voltage and current
Check loop resistance, 250
Ω
minimum (PS voltage -transmitter voltage/loop current)
HART message reading:
“Configuration not update due to brown-out.”
Cycle power and repeat configuration change
Содержание 4600
Страница 2: ......
Страница 4: ......
Страница 8: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 TOC 4 ...
Страница 20: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 2 10 ...
Страница 54: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 4 12 ...
Страница 64: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 B 2 ...
Страница 67: ......