Reference Manual
00809-0100-4022, Rev AA
July 2002
3-17
Model 4600
HART Communicator
To initiate a loop test, perform the following procedure:
1. Connect a reference meter to the transmitter by shunting transmitter
power through the meter at some point in the loop.
2. From the
Home
screen, enter the fast key sequence below “Loop Test”
to verify the output of the transmitter.
3. Select
OK
after the control loop is set to manual (see “Setting the Loop
to Manual” on page 3-2).
4. Select a discrete milliamp level for the transmitter to output. At the
Choose Analog Output
prompt select 1: 4mA, select 2: 20mA, or select
3: “Other” to manually input a value.
a. If you are performing a loop test to verify the output of a transmitter,
enter a value between 4 and 20 mA.
b. If you are performing a loop test to verify alarm levels, enter the
milliamp value representing an alarm state (see Tables 3-1, 3-2, and
3-2 on page 3-10).
5. Check the reference meter installed in the test loop to verify that it
displays the commanded output value.
a. If the values match, the transmitter and the loop are configured and
functioning properly.
b. If the values do not match, the current meter may be attached to the
wrong loop, there may be a fault in the wiring, the transmitter may
require an output trim, or the reference meter may be
malfunctioning.
After completing the test procedure, the display returns to the loop test screen
to choose another output value or to end loop testing.
Содержание 4600
Страница 2: ......
Страница 4: ......
Страница 8: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 TOC 4 ...
Страница 20: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 2 10 ...
Страница 54: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 4 12 ...
Страница 64: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 B 2 ...
Страница 67: ......