background image

Reference Manual

00809-0100-4022, Rev AA

July 2002

Model 4600

3-10

DETAILED SETUP

Failure Mode Alarm and 
Saturation

The Model 4600 transmitter automatically and continuously perform 
self-diagnostic routines. If the self-diagnostic routines detect a failure, the 
transmitter drives the output to configured alarm values. The transmitter will 
also drive the output to configured saturation values if the applied pressure 
goes outside the 4-20 mA range values.

NOTE

The failure mode alarm direction can also be configured using the HART 
Communicator or AMS.

NOTE

Under some failure conditions, the transmitter will ignore user configured 
alarm conditions and drive the transmitter to low alarm.

The Model 4600 transmitter have three configurable options for failure mode 
alarm and saturation levels:

• Rosemount (Standard), see Table 3-1
• Custom, see Table 3-2

Table 3-1.  Rosemount 

(Standard) Alarm and Saturation 

Values

Table 3-2.  Custom Alarm and 

Saturation Values

Failure mode alarm and saturation levels can be configured using a HART 
Communicator or AMS, see “Alarm and Saturation Level Configuration” on 
page 3-11. Per Table 3-2, custom alarm and saturation levels can be 
configured between 3.6 mA and 3.9 mA for low values and between 20.1 mA 
and 23 mA for high values. The following limitations exist for custom levels:

• Low alarm level must be less than the low saturation level
• High alarm level must be higher than the high saturation level
• High saturation level must not exceed 21.5 mA
• Alarm and saturation levels must be separated by at least 0.1 mA

The HART Communicator or AMS will provide an error message if a 
configuration rule is violated.

Level

4–20 mA Saturation

4–20 mA Alarm

Low

3.9 mA

 3.75 mA

High

20.8 mA

 21.75 mA

Level

4–20 mA Saturation

4–20 mA Alarm

Low

3.7 mA — 3.9 mA

3.6 mA — 3.8 mA

High

20.1 mA — 21.5 mA

20.2 mA — 23.0 mA

Содержание 4600

Страница 1: ...www rosemount com Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 Oil Gas Panel Transmitter ...

Страница 2: ......

Страница 3: ...nd order related questions United States 1 800 999 9307 7 00 am to 7 00 pm CST Asia Pacific 65 777 8211 Europe Middle East Africa 49 8153 9390 North American Response Center Equipment service needs 1 800 654 7768 24 hours includes Canada Outside of these areas contact your local Rosemount representative The products described in this document are NOT designed for nuclear qualified applications Usi...

Страница 4: ......

Страница 5: ...6 Wiring 2 6 Signal Wiring Grounding 2 6 Power Supply 4 20 mA Transmitters 2 6 Surges Transients 2 7 Optional Transient Protection 2 7 Zero the transmitter 2 7 Re zeroing 2 8 HART Communicator 2 8 Using the transmitter zero adjustment target 2 8 Hazardous Locations 2 8 Grounding the Transmitter Case 2 9 SECTION 3 Configuration Overview 3 1 Safety Messages 3 1 Warnings 3 1 Commissioning on the Benc...

Страница 6: ...ation Level Configuration 3 11 HART Communicator 3 11 AMS 3 11 Alarm and Saturation Levels for Burst Mode 3 11 Alarm and Saturation Values for Multidrop Mode 3 12 Alarm Level Verification 3 12 Process Alerts 3 12 HART Communicator 3 12 AMS 3 13 Scaled Variable Configuration 3 13 HART Communicator 3 14 AMS 3 15 Re mapping 3 15 HART Communicator 3 15 AMS 3 16 Sensor Temperature Unit 3 16 AMS 3 16 Di...

Страница 7: ...g a Trim Procedure 4 5 Sensor Trim 4 5 Zero Trim 4 6 HART Communicator 4 6 AMS 4 6 Full Trim 4 7 HART Communicator 4 7 AMS 4 7 Recall Factory Trim 4 8 Recall Factory Trim Sensor Trim 4 8 AMS 4 8 Recall Factory Trim Analog Output 4 8 AMS 4 8 Analog Output Trim 4 9 Digital to Analog Trim 4 9 HART Communicator 4 9 AMS 4 10 Digital to Analog Trim Using Alternate Scale 4 11 AMS 4 11 SECTION 5 Troublesh...

Страница 8: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 TOC 4 ...

Страница 9: ...installation instructions Section 3 Configuration provides instruction on commissioning and configuring the Model 4600 transmitter Information on software functions configuration parameters and online variables is also included Section 4 Operation and Maintenance contains operation and maintenance instructions Section 5 Troubleshooting provides troubleshooting techniques for the most common operat...

Страница 10: ...ill provide a Return Material Authorization RMA number The center will also ask for the process material to which the product was last exposed Rosemount National Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances Individuals who handle products exposed to a hazardous substance can avoid injury if they are...

Страница 11: ...mitter to describe basic mounting and wiring procedures for initial installation HART Communicator and AMS instructions are provided to allow users to perform configuration functions For convenience HART Communicator fast key sequences are provided and labeled Fast Keys for each software function below the appropriate headings SAFETY MESSAGES Procedures and instructions in this section may require...

Страница 12: ...h the transmitter Flush lines with the blocking valves closed and refill lines with water before resuming measurement Explosions can result in death or serious injury Transmitters located in hazardous areas should be installed in accordance with local codes and requirements for that area Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations ...

Страница 13: ... Section 3 Set Units Set Range Points Set Output Type Set Damping Verify Apply Pressure Yes Within Specifications Yes No Refer to Section 5 Troubleshooting Mount Transmitter page 2 4 Wire Transmitter pages 2 6 2 9 Power Transmitter page 2 6 Zero Out Sealed Gauge Effects page 2 7 Done Confirm Transmitter Configuration page 3 5 Confirm Transmitter Configuration page 3 21 ...

Страница 14: ...ess Connection 1 Hand tighten the appropriate sized impulse piping into the process connection 2 Using a wrench on the hex flat at the impulse piping connection apply enough torque to prevent the process fluid from leaking Do not exceed 100 ft lbs NOTE Apply torque only to the hex flat located at the process end of the transmitter Do not apply torque to the transmitter body or electrical connectio...

Страница 15: ...e slope the impulse piping at least 1 inch per foot 8 cm per m upward from the transmitter toward the process connection For gas service slope the impulse piping at least 1 inch per foot 8 cm per m downward from the transmitter toward the process connection Avoid high points in liquid lines and low points in gas lines Use impulse piping large enough to avoid friction effects and blockage Vent all ...

Страница 16: ...option specified Figure 2 2 Model 4600 Field Wiring Signal Wiring Grounding Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment Power Supply 4 20 mA Transmitters The dc power supply should provide power with less than two percent ripple Total resistance load is the sum of resistance from signal leads and the load resistance of the controller indic...

Страница 17: ...ption Option Code T1 in the transmitter model number Transient protection can not be added to units ordered without the T1 option Zero the transmitter Performing a zero adjustment is a recommended step for sealed gauge transmitters NOTE Do not re zero absolute transmitters Re zeroing the transmitter allows for a single point adjustment to compensate for any mounting position and sealed gauge effec...

Страница 18: ...ter 2 Set the 4mA point by touching the magnetic end of the provided adjustment tool to the zero target Z on the transmitter You must maintain contact for at least two seconds but no longer than ten seconds for the zero function to activate 3 Verify that the output is 4mA HAZARDOUS LOCATIONS The Model 4600 transmitter has an explosion proof housing Individual transmitters are clearly marked with a...

Страница 19: ...mitters External Ground Assembly This assembly is included with the optional transient protection Option Code T1 The External Ground Assembly can also be ordered with the transmitter Option Code D4 or as a spare part 4600 0113 0001 NOTE Grounding the transmitter case using the threaded electrical or process connections may not provide a sufficient ground The transient protection Option Code T1 wil...

Страница 20: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 2 10 ...

Страница 21: ...HART Communicator fast key sequences are labeled Fast Keys for each software function below the appropriate headings SAFETY MESSAGES Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Refer to the following safety messages before ...

Страница 22: ...le communication a resistance of at least 250 ohms must be present between the HART Communicator loop connection and the power supply Do not use inductive based transient protectors with more than 3 mH of inductance with the Model 4600 transmitter When using a HART Communicator any configuration changes made must be sent to the transmitter by using the Send key F2 AMS configuration changes are imp...

Страница 23: ... key or log into AMS The HART Communicator or AMS will search for a HART compatible device and indicate when the connection is made If the HART Communicator or AMS fail to connect it indicates that no device was found If this occurs refer to Section 5 Troubleshooting Figure 3 1 Bench Wiring 4 20 mA Bench Wiring RL 250 ohm Current Meter Power Supply 275 Hart Communicator Model 4600 4600_4022WIRING1...

Страница 24: ... 2 3 2 1 Field Device Information 1 4 4 1 Loop Test 1 2 2 Lower Sensor Trim 1 2 3 3 2 Message 1 3 4 3 Number of Requested Preambles 1 4 3 3 2 Pressure Alert Config 1 4 3 5 3 Poll Address 1 4 3 3 1 Poll a Multidropped Transmitter Left Arrow 4 1 1 Re mapping 1 4 3 6 4 Rerange Keypad Input 1 2 3 1 1 Saturation Level Config 1 4 2 7 8 Scaled D A Trim 4 20 mA Output 1 2 3 2 2 Scaled Variable Config 1 4 ...

Страница 25: ...view the transmitter configuration data Fast Keys 1 5 PV Lower Sensor Limit LSL Tag PV Upper Sensor Limit USL Date PV Lower Range Value LRV Descriptor PV Upper Range Value URV Message PV minimum span Write protect Lower sensor trim point Local keys Upper sensor trim point Universal revision Sensor trim calibration type Field device revision Damping Software revision Alarm direction Hardware revisi...

Страница 26: ...readings within the digital limits of the sensor For example if the 4 and 20 mA points are set to 0 and 1 000 psi and the transmitter detects a pressure of 2 500 psi it digitally outputs the 2 500 psi reading and a 250 of span reading However there may be up to 5 0 error associated with output outside of the range points AMS Right click on the device and select Process Variables from the menu The ...

Страница 27: ...r range values as often as necessary to reflect changing process conditions Changing the lower or upper range point results in similar changes to the span NOTE Transmitters are shipped from Rosemount Inc fully calibrated per request or by the factory default of full scale span upper range limit Use one of the methods below to rerange the transmitter Each method is unique examine all options closel...

Страница 28: ...mit the upper range point is automatically set to the sensor limit and the span is adjusted accordingly 1 From the HOME screen enter the fast key sequence shown to configure lower and upper range values and follow the on line instructions Rerange with a Pressure Input Source and the Local Zero and Span Targets option D1 1 For Zero based lower range values gauge only Vent the transmitter For Non Ze...

Страница 29: ...alues 3 Select Exit to leave the Apply Values screen 4 Select Next to acknowledge the loop can be returned to automatic control 5 Select Finish to acknowledge the method is complete Damping The Damp command introduces a delay in processing which increases the response time of the transmitter smoothing variations in output readings caused by rapid input changes Determine the appropriate damp settin...

Страница 30: ... see Table 3 1 Custom see Table 3 2 Table 3 1 Rosemount Standard Alarm and Saturation Values Table 3 2 Custom Alarm and Saturation Values Failure mode alarm and saturation levels can be configured using a HART Communicator or AMS see Alarm and Saturation Level Configuration on page 3 11 Per Table 3 2 custom alarm and saturation levels can be configured between 3 6 mA and 3 9 mA for low values and ...

Страница 31: ...k Next after setting the control loop to manual 2 Click Next after acknowledging the current alarm levels 3 Select the desired alarm settings NAMUR Rosemount Other 4 If Other is selected enter desired HI Value and LO Value custom values 5 Click Next to acknowledge new alarm levels 6 Select Next to acknowledge the loop can be returned to automatic control 7 Select Finish to acknowledge the method i...

Страница 32: ...figured data point is exceeded Process alerts can be set for pressure temperature or both A process alert will be transmitted continuously if the pressure or temperature set points are exceeded and the alert mode is ON An alert will be displayed on a HART Communicator or AMS status screen The alert will reset once the value returns within range NOTE HI alert value must be higher than the LO alert ...

Страница 33: ...ct OK Scaled Variable Configuration The scaled variable configuration allows the user to create a relationship conversion between the pressure reading and custom units The scaled variable configuration defines the following items Scaled variable units Custom units to be displayed Scaled data options Defines the transfer function for the linear application Pressure value position 1 Lower known valu...

Страница 34: ...lationship between PV and scaled variable units are linear Linear prompts for two data points 5 Enter pressure value position 1 Pressure values must be within the range of the transmitter a Enter the lower known value point considering any linear offset 6 Enter scaled variable position 1 a Enter the lower known value point this value must be no longer than seven digits 7 Enter pressure value posit...

Страница 35: ...e and click Next 14 Select Next to acknowledge that the loop can be returned to automatic control 15 Select Finish to acknowledge the method is complete Use the following example to complete a Scaled Variable configuration Re mapping The re mapping function allows the transmitter primary secondary and tertiary variables to be configured as desired Default configuration for transmitter variables is...

Страница 36: ...ormation and click OK 5 After carefully reading the warning select OK DIAGNOSTICS AND SERVICE Diagnostics and service functions listed below are primarily for use after field installation The Transmitter Test feature is designed to verify that the transmitter is operating properly and can be performed either on the bench or in the field The Loop Test feature is designed to verify proper loop wirin...

Страница 37: ...ally input a value a If you are performing a loop test to verify the output of a transmitter enter a value between 4 and 20 mA b If you are performing a loop test to verify alarm levels enter the milliamp value representing an alarm state see Tables 3 1 3 2 and 3 2 on page 3 10 5 Check the reference meter installed in the test loop to verify that it displays the commanded output value a If the val...

Страница 38: ...wledge the method is complete ADVANCED FUNCTIONS FOR HART PROTOCOL Saving Recalling and Cloning Configuration Data Use the cloning feature of the HART Communicator or the AMS User Configuration feature to configure several Model 4600 transmitter similarly Cloning involves configuring a transmitter saving the configuration data then sending a copy of the data to a separate transmitter Several possi...

Страница 39: ...er 12 Select OK after the control loop is set to manual 13 After the configuration has been sent select OK to acknowledge that the loop can be returned to automatic control When finished the HART Communicator informs you of the status Repeat Steps 3 through 13 to configure another transmitter NOTE The transmitter receiving cloned data must have the same software version or later as the original tr...

Страница 40: ...nfiguration to the target device as desired Click OK to apply the configuration and close the window Burst Mode When configured for burst mode the Model 4600 provides faster digital communication from the transmitter to the control system by eliminating the time required for the control system to request information from the transmitter Burst mode is compatible with the analog signal Because the H...

Страница 41: ...he host and the transmitters takes place digitally with the analog output of the transmitters deactivated Up to fifteen transmitters can be connected on a single twisted pair of wires Multidrop installation requires consideration of the update rate necessary from each transmitter the combination of transmitter models and the length of the transmission line Communication with transmitters can be ac...

Страница 42: ... in a multidropped loop must have a unique poll address HART Communicator 1 From the HOME screen enter the fast key sequence shown AMS Right click on the device and select Configuration Properties from the menu 1 In the HART tab in ID box enter poll address located in the Poll addr box click Apply 2 An Apply Parameter Modification screen appears enter desired information and click OK 3 After caref...

Страница 43: ...ch the plant standard or the control loop The Model 4600 uses a microprocessor that contains information about the sensor s specific characteristics in response to pressure and temperature inputs A smart transmitter compensates for these sensor variations The process of generating the sensor performance profile is called factory characterization Factory characterization also provides the ability t...

Страница 44: ...n 3 Corrections are performed in the microprocessor to obtain a digital representation of the process input Digital PV 4 The Digital PV is converted to an analog value Digital to Analog Signal Conversion Figure 4 1 also identifies the approximate transmitter location for each calibration task Data flows from left to right and a parameter change affects all values to the right of the changed parame...

Страница 45: ...es for each type of Model 4600 transmitter for bench or field calibration Figure 4 1 Transmitter Data Flow with Calibration Options Transmitter Electronics Module Microprocessor Digital PV Sensor Input Device Output Device 20 00 mA 4600 PT 4763 1 Device Setup Online 2 PV 1000 PSI 3 AO 20 00 mA 4 LRV 0 00 PSI 5 URV 1000 PSI Input Pressure Analog Output HART Communicator NOTE Value on PV line should...

Страница 46: ...lation Step 1 Determine the performance required for your application Step 2 Determine the operating conditions Step 3 Calculate total probable error TPE Step 4 Calculate the stability per month Step 5 Calculate calibration frequency Required Performance 1 1 of span Transmitter Model 4600G Range 4 Calibrated Span 4000 psig Ambient Temperature Change 50 F TPE 0 572 of span Where Reference Accuracy ...

Страница 47: ...dependent Both trim functions alter the transmitter s interpretation of the input signal Zero trim is a single point adjustment It is useful for compensating for mounting position and sealed gauge effects Since this correction maintains the slope of the characterization curve it should not be used in place of a full trim over the full sensor range When performing a zero trim ensure that the transm...

Страница 48: ...the zero trim function as follows 1 Vent the transmitter and attach a HART Communicator to the measurement loop 2 From the Home screen follow the fast key sequence shown 3 Follow the commands provided by the HART Communicator to complete the zero trim adjustment AMS Right click on the device and select Calibrate then Zero trim from the menu 1 Click Next after setting the control loop to manual 2 C...

Страница 49: ...0 mA points Do not attempt to obtain reverse output by reversing the high and low points The transmitter allows approximately five percent URL deviation from the characterized curve established at the factory 4 Follow the commands provided by the HART Communicator to complete the adjustment of the lower value 5 Repeat the procedure for the upper value replacing 2 Lower sensor trim with 3 Upper sen...

Страница 50: ...ick Next to acknowledge restoration of trim values is complete 4 Select Next to acknowledge the loop can be returned to automatic control 5 Select Finish to acknowledge the method is complete Recall Factory Trim Analog Output This command resets the transmitter analog output trim to the as shipped factory settings The Recall Factory Trim Analog Output command can be useful for recovering from an i...

Страница 51: ...ce Meter prompt Connect in series with the signal loop or shunt power through the reference meter at some point 3 Select OK after connecting the reference meter 4 Select OK at the Setting Fld Dev Output To 4 MA prompt The transmitter outputs 4 0 mA 5 Record the actual value from the reference meter and enter it at the Enter Meter Value prompt The HART Communicator prompts you to verify whether or ...

Страница 52: ...m the reference meter and enter it at the Enter meter value screen and click Next 5 Select Yes if the reference meter value equals the transmitter output value or No if it does not Click Next a If Yes is selected proceed to Step 6 b If No is selected repeat Step 4 6 Click Next at the Setting fld dev output to 20mA screen 7 Repeat Step 4 Step 5 until the reference meter equals the transmitter outpu...

Страница 53: ...t Calibrate then Scaled D A trim from the menu 1 Click Next after setting the control loop to manual 2 Select Change to change scale click Next 3 Enter Set scale Lo output value click Next 4 Enter Set scale Hi output value click Next 5 Click Next to proceed with Trim 6 Click Next after connecting the reference meter 7 Click Next at the Setting fld dev output to 4 mA screen 8 Record the actual valu...

Страница 54: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 4 12 ...

Страница 55: ...SAFETY MESSAGES Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises potential safety issues is indicated by a warning symbol Refer to the following safety messages before performing an operation preceded by this symbol Warnings Explosions can result in death or serious injury Transmitter...

Страница 56: ...ied pressure is between the 4 and 20 mA set points Verify output is not in alarm condition Verify transmitter is not in Loop Test mode Digital Pressure Variable reading is low or high Check test equipment verify accuracy Check impulse piping for blockage or low fill in wet leg Verify transmitter is calibrated properly Verify pressure calculations for application Digital Pressure Variable reading i...

Страница 57: ...nformance to at lease 3 sigma Reference Accuracy For zero based spans reference conditions silicone oil fill SST materials digital trim values set to equal range points Includes the effects of terminal based linearity hysteresis and repeatability 0 25 of calibrated span from 1 1 to 30 1 rangedown Long Term Stability 0 5 of span for 3 years under normal operating conditions Vibration Effect Less th...

Страница 58: ...e to any host that conforms to the HART protocol Power Supply External power supply required Standard transmitter 4 20 mA operates on 11 25 to 42 4 V dc with no load Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply as described by Overpressure Limits Transmitters withstand the following pressure without damage Range 4 6 000 psi Model 4600 Oil...

Страница 59: ...le from 0 3 to 60 seconds for one time constant This software damping is in addition to sensor module response time Failure Mode Alarm HART 4 20mA output code A If self diagnostics detect a gross transmitter failure the analog signal will be driven offscale to alert the user Rosemount standard and custom alarm levels are available see Table A 1 below High or low alarm signal is software selectable...

Страница 60: ... process seal design meets the requirements NEC 2002 section 501 5 F 3 505 16 E 3 and API 14F 14FZ 6 8 2 2 No additional process sealing is required Process Wetted Parts Process Isolating Diaphragms 316L SST Hastelloy C 276 Sensor Module Fill Fluid Silicone Ordinary Locations Certifications As standard the transmitter has been examined and tested to determine that the design meets basic electrical...

Страница 61: ...July 2002 A 5 Model 4600 DIMENSIONAL DRAWINGS Model 4600 Oil Gas Panel Transmitter Electrical Connection 14 NPT 6 6 167 6 1 5 38 1 Diameter Process Connection Optional Ground Screw Ordering Option D4 NOTE Dimensions are in inches millimeters ...

Страница 62: ...re Configuration Alarm Limits C6 Custom alarm saturation signal levels high alarm C7 Custom alarm saturation signal levels low alarm Hardware Adjustments D1 Zero Span Adjustments External Ground Screw Assembly D4 External Ground Screw Assembly Safety Approvals E5 FM explosion proof flameproof Special Certifications Q4 Calibration Data Certificate Transient Protection T1 Transient protection Typica...

Страница 63: ...formation Factory Mutual FM Approvals Certificate No 3012302 E5 Explosion proof for Class I Division I Groups B C and D Dust Ignition proof for Class II Division I Groups E F and G Class III Division I 40 F 40 C Tamb 185 F 85 C Hazardous classified locations Conduit seal not required Enclosure Type 4X ...

Страница 64: ...Reference Manual 00809 0100 4022 Rev AA July 2002 Model 4600 B 2 ...

Страница 65: ...6 Loop Test 3 16 Transmitter test 3 16 Diagrams Bench hook up 3 3 Field hook up 3 3 Multidrop network 3 21 Typical multidrop network 3 21 Digital to analog trim 4 9 Other scale 4 11 Disassembly Before disassembling 5 2 Disassembly procedures 5 2 F Failure mode alarm and saturation Values 3 10 Full trim 4 7 G Grounding 2 9 External assembly 2 9 Internal connection 2 9 Signal wiring grounding 2 6 H ...

Страница 66: ...figuration 3 13 Sensor Temperature 3 6 Sensor temperature 3 6 Unit 3 16 Sensor trim 4 5 Service and Diagnostics 3 16 Service Support 1 2 Setup Basic 3 7 Detailed 3 10 Signal wiring grounding 2 6 Surges 2 7 T Tagging 2 2 Test 3 16 Transient Protection 2 7 Transients 2 7 Transmitter functions 4 1 Transmitter test 3 16 Trim Analog output 4 9 Digital to Analog 4 9 Other scale 4 11 Full 4 7 Recall fact...

Страница 67: ......

Страница 68: ...rs HART is a registered trademark of the HART Communication Foundations Foundation is a trademark of the Fieldbus Foundation Hastelloy and Hastelloy C are registered trademarks of Haynes International Cover photo 4600h0101 tif Rosemount Inc 8200 Market Boulevard Chanhassen MN 55317 USA T U S 1 800 999 9307 T International 952 906 8888 F 952 949 7001 www rosemount com Fisher Rosemount GmbH Co Shipp...

Отзывы: