5-3
Specifications and Reference Data
Institut Scientifique de Service Public (ISSeP)/CENELEC Flameproof
Approval
E9
EEx d IIC T6 (T
amb
= –20 to 60 °C)
British Approvals Service for Electrical Equipment in Flammable
Atmospheres (BASEEFA) Approvals
N1
Type
N
Approval
Ex N IIC T6 (T
amb
= –40 to 50 °C)
Ex N IIC T5 (T
amb
= –40 to 75 °C)
Special Conditions for Safe Use (x):
The transmitter is not capable of withstanding the electrical
strength test required by BS 6941, Clause 6.1 (1998). This condition
must be taken into account during installation.
I1
CENELEC
Intrinsic
Safety,
EEx ia IIC T6 (T
amb
= –40 to 50 °C)
EEx ia IIC T5 (T
amb
= –40 to 75 °C)
Input Entity Parameters:
Special Conditions for Safe Use (x):
The transmitter is not capable of withstanding the insulation test
required by EN50 020, Clause 5.7 (1977). This condition must be
taken into account during installation.
Standard Australia Quality Assurance Services (SAA)
E7
Flameproof
Approval
Ex d IIC T6 (T
amb
= –20 to 60 °C)
N7
Type
N
Approval
Ex n IIC T6 (T
amb
= –40 to 50 °C)
Ex n IIC T5 (T
amb
= –40 to 75 °C)
I7
Intrinsic
Safety
Ex ia IIC T5 (T
amb
= –40 to 75 °C)
Power/Loop
Sensor
U
max:in
= 30 V dc
U
max:in
= 4.5 V dc
I
max:in
= 300 mA
I
max:in
= 51 mA
P
max:in
= 1.0 W
P
max:in
= 0.057 W
C
eq
= 0.005 µF
U
max:out
= 24.2 V dc
L
eq
= 20 µH
I
max:out
= 35 mA
P
max:out
= 0.041 W
C
a
= 0.2 µF (Group IIC)
L
a
= 31 mH (Group IIC)
C
a
= 0.6 µF (Group IIB)
L
a
= 93 mH (Group IIB)
C
a
= 1.6 µF (Group IIA)
L
a
= 248 mH (Group IIA)