Rosemount Models 3144 and 3244MV Smart Temperature Transmitters
C-6
NOTE
Certain tasks require that you set the control loop to manual control
before completing them. One of the Function Key Sequence steps often
includes the warning to return the loop to manual. If the loop is not in
manual control, be sure to watch for this screen. If it comes up during
the Function Key sequence, set the loop to manual before continuing
with the task.
Function Key Sequence
Examples
Date
To change the Date following the Menu Structure, start at the Home
Menu and press F3 for
Configure
, F3 for
Xmtr Info
, and F1 three
times in a row to reach the Date function. The Function Key Sequence
is F3, F3, F1(×3).
Loop Test
To perform the Loop Test, start at the Home Menu and press F2 for
Test
, F3 for
Loop Test
, and F4 for
Proceed
(after the loop is set to
manual). The Function Key Sequence is F2, F3, F4.
Diagnostics Messages
The following provides a guide to Model 268 HART Communicator
diagnostic messages.
Message
Description
CAUTION–Progressing
will clear Ofln Mem
OFLN Memory is cleared for new information.
Data saved in OFLN
Mem for downloading
Off-line configuration data are saved in the Off-line Memory and can
be downloaded or sent to the transmitter at an appropriate time.
Different XMTR type
connected–XMTR Mem
not changed
Transmitter did not accept data sent because the data is meant for
a different type of transmitter.
End of List
Marks the end of a list of diagnostic messages.
ERR–Hard/software is
not compatible
Transmitter cannot interpret Model 268 message. Perform a
transmitter test. If OK, make note of conditions and keystrokes
leading to failure, and contact Rosemount Service Center.
ERR–Not in output
mode
Transmitter must be in output mode to complete this operation.
ERR–Not xmtr
command
Transmitter does not understand the command sent by the Model
268. Press F4, RESTART to restart the transmitter, or press F3 to
suppress the error message ad REVIEW the software revision level.
You may need to contact the Rosemount Service Center.
ERR–Out of range
The value chosen is outside the sensor range limits. Enter an
acceptable value.
ERR–PV out of limits
The transmitter is in a high flow rate condition or has experienced a
sensor failure.
ERR–Update failure
The Model 268 has missed several communications from the
transmitter. Check for noise on the loop and adjust filters. If no noise
is present, test the Model 268 and the transmitter.
ERR–Value was too hi
Enter an acceptable value.
ERR–Value was too lo
Enter an acceptable value.
ERR–Xmtr fault
support command
Model 268 is detecting a possible problem with the transmitter.
Perform the transmitter self-test and use the diagnostic messages
to locate the problem.
ERR–Xmtr will not
support command
The transmitter does not understand the Model 268 command.
Press F4, RESTART or press F3, REVIEW to review the software
revision level of the transmitter. Check compatibility.
ERR–268 Data err
Transmitter cannot interpret Model 268 inquiry. Perform a
transmitter test. If OK, make note of conditions and keystrokes
leading to failure, and contact Rosemount Service Center.