Rosemount Model 3144 and 3244MV Smart Temperature Transmitters
4-6
Assembling the
Electronics Housing
Replacing the Electronics
Module
Use the following procedure to reassemble the electronics housing for
the Model 3144 and 3244MV transmitters:
1. Examine the electronics module to ensure that the failure mode
and transmitter security jumpers are in the desired positions.
2. Carefully insert the electronics module to mate the
interconnecting pins with the necessary receptacles on the
electronics board.
3. Tighten the two mounting screws. Replace the LCD meter, if
applicable.
4. Replace the cover. Tighten
1
/
6
of a revolution after the cover
begins to compress the O-ring. Both transmitter covers must be
fully engaged to meet explosion proof requirements.
RETURN OF MATERIALS
To expedite the return process, call the Rosemount North American
Response Center toll-free at 800-654-7768. This center, available 24
hours a day, will assist you with any needed information or materials.
The center will ask for product model and serial numbers, and will
provide a Return Material Authorization (RMA) number. The center
will also ask for the name of the last process material to which the
product was exposed, and will detail the additional information and
procedures necessary to return goods exposed to hazardous substances.
If a hazardous substance is identified, a Material Safety Data Sheet
(MSDS), required by law to be available to people exposed to specific
hazardous substances, must be included with the returned materials.
See “Safety Messages” on page 4-1 for complete warning information.