Determine where in the rack, the subsystem is going to
be installed.
CAUTION!
The mounting positions must be carefully measures so that rails
can be mounted parallel to each other.
•
Use the figure below to measure the relative locations
of the cage nuts on the rack posts (if they do not have
threaded holes). There are 5 holes between clip nuts.
Attach two M5 clip nuts (#07) on each of the front rack
posts.
Attaching Cage Nuts to a Front Rack Post
•
Adjust the length of the rail assembly and make sure
the bend of the L-shape rail (#01) faces inward.
Adjust Rail Length
•
Position the front-end of a rail below the top clip nut.
Secure the rail to the front and rear rack posts each
using two position screws (#08). (See figure below) Do
not insert the screws into the cage nuts as cage nuts
will be used to secure the enclosure later.