Unit functions
Page 38
RESM-5
Part 1 of 3: Error messages (faults)
NOTE:
The error messages shown here are output as faults (a constant error voltage appears at the actual
value output
;
the alarm output is energized).
Error
code
Act. val.
output
voltage
[V]
Cause
Action if machine
started for first time
Action if machine
already operating, HS
band not changed
1
101
0.66
No current signal
Fault area
Fault area
2
102
1.33
No voltage signal
Fault area
Fault area
118
Voltage signal has wrong
polarity
(
Reconnect/
Interchange U
R
measuring wire to
terminals 8+9
Reconnect/
Interchange U
R
measuring wire to
terminals 8+9
3
103
2.00
No current / voltage signals
Fault area
Fault areas
120
STANDBY test failed
4
107
2.66
Temperature step, down
Fault areas
(loose contact)
Fault areas
(loose contact)
108
Temperature step, up
109
Maximum temperature
exceeded
Check application
Check application
307
Temperature too low / high
308
309
310
5
201
3.33
Line frequency missing /
fluctuates
Check power supply
Check power supply
202
Line frequency too high /
fluctuates
203
Line frequency too low /
fluctuates
6
304
4.00
Heatup time too long
Run RESET
Run RESET