Unit functions
Page 30
RESM-5
228
Screensaver
To extend the life of the OLED display, you can
specify the time here after which it is dimmed.
If you set "0min", the display is not dimmed. The
display lights up again as soon as a key is pressed,
an alarm occurs, or an input signal is activated.
0 (=off)…20min
229
ALARM-IN/RESET
input
This menu step configures the behavior of the
ALARM-IN/RESET input.
• normal: An active alarm is reset if the ALARM-
IN/RESET input (terminal 7) is energized.
• normal w. STANDBY survey: An active alarm is
reset if the ALARM-IN/RESET input (terminal 7)
is energized. The RESM-5 generates error
message 120 "STANDBY not observed" if the
main controller controls the heatsealing band
(measuring impulses or control mode) while the
ALARM-IN/RESET input is energized.
• inverse: An active alarm is reset if the
ALARM-IN/RESET input (terminal 7) is de-
energized.
• inverse w. STANDBY survey: An active alarm is
reset if the ALARM-IN/RESET input (terminal 7)
is de-energized. The RESM-5 generates error
message 120 "STANDBY not observed" if the
main controller controls the heatsealing band
(measuring impulses or control mode) while the
ALARM-IN/RESET input is de-energized.
normal
normal w. STAND-
BY survey
inverse
inverse w. STAND-
BY survey
No.
Name
Description
Setting range