Unit functions
RESM-5
Page 31
9.6
Monitoring temperature setting
(maximum temperature set point)
You can set the maximum temperature on the
RESISTRON monitoring device RESM-5 with menu
step 206.
The maximum value of the setting range is
limited by the temperature range specified
with step 205 in the Configuration menu.
The set point selected for the heatsealing temperature
must be at least 40°C.
The set maximum temperature is displayed in the main
menu after it has been entered.
To prevent dangerous situations, refer to the
risk analysis for the machine or plant.
9.7
Temperature indication / actual
value output
If the display is in the home position, the ACTUAL tem-
perature is indicated there both as a digital value and as
a progress bar.
The heating and control process can thus be observed
at any time.
The RESISTRON monitoring device RESM-5 addition-
ally supplies an electrically isolated, analog 0…10VDC
signal, which is proportional to the real ACTUAL tem-
perature, at terminals 17+14.
Voltage values:
0VDC
0°C
10VDC
300°C or 500°C
(depending on the unit configuration)
The relationship between the change in the output
voltage and the ACTUAL temperature is linear.
!
!
RESM-5
17
max. 5mA
14
GND
33Ohm
Act. value
output
0…10VDC
-
+
0…10VDC
Temperature
meter
e.g. ATR-3
+
0 - 300°C range
1
2
3
4
5
6
7
8
9 10
300
Te
m
p
er
a
tu
re
T
°C
20°C
"ZERO"
VDC
Voltage U
60
90
120
150
180
210
240
270
0.66V