Device functions
Page 23
UPT-6011
Version 5
8.2
EtherNet/IP
TM
communication
The following sections only describe controller-specific functions. For general information on the EtherNet/IP
TM
interface and the system configuration, please refer to the description of your PLC.
The controller can communicate via the EtherNet/IP
TM
interface provided the 24 VDC supply voltage
(terminals 5+7) is present.
As long as no line voltage is present, the controller remains in an inactive status.
But interruption of the line voltage (e.g. by being switched off when a door is opened) triggers the error message
201 (error group no. 7, network voltage/sync signal is missing) and the Alarm relay switches. This is caused by
the lack of line voltage. The error message can be reset by switching on the line voltage again and setting the
RS bit (
section 8.5.3 "Reset (RS)" on page 26).
You can easily process the error code that appears if the line voltage is switched off – or suppress switching of
the alarm relay – in the PLC program.
8.3
Device description file (EDS)
The configuring tools for the EtherNet/IP
TM
scanner interpret the content of the device description file (EDS) and
use this information to create a parameter set for the EtherNet/IP
TM
scanner which controls user data traffic. The
ROPEX_UPT-6011_V2_5.eds file of the UPT-6011 contains all essential controller information for the configura-
tion, e.g. the I/O data description, parameter descriptions etc. The device description files and the associated
image files (.BMP and .ICO) can be requested by e-mail (
) or downloaded from our website
HEAT
(yellow)
—
START requested
but function blocked (e.g.
AUTOCAL active, set tem-
perature < 40 °C)
START executing
OUTPUT
(green)
In control mode, luminous intensity is proportional to heating current.
ALARM
(red)
Configuration error, no
AUTOCAL possible
Controller calibrated incor-
rectly, run AUTOCAL
Error,
section 8.19
MODULE STATUS
Green: Standby
Red: Warning, e.g. rotary
coding switch setting
changed
Red / green: Self-test
Green: Normal operation
Red: Serious communica-
tion error
NETWORK
STATUS
Green: No connection but
IP address received
Red: Connection timeout
Red / green: Self-test
Green: At least one con-
nection to scanner
Red: IP address of con-
troller already assigned
LINK PORT 1, 2
(green)
—
—
Connection exists to
Ethernet
RX / TX PORT 1, 2
(yellow)
Device is transmitting / receiving Ethernet frames
LED
Blinks slowly (1 Hz)
Blinks fast (4 Hz)
Lit continuously