Device functions
Version 5
UPT-6011
Page 30
Behaviour of the temperature controller
In order to be able to assess the behaviour of the temperature controller, you will find examples of the statuses of
the voltage supply and the resulting statuses of the controller in the table. The table represents a chronological
sequence.
24 V
supply of
the con-
troller
Line
voltage
Bit
set (1) or not set (0)
Status of bits/result
Input data
Output data
1.
Off
Off
Temperature controller and control
of the machine do not communi-
cate.
2.
On
Off
RS bit = 0
SA bit = 1
AL bit = 0
No reset, standby active, no alarm
The SA bit is active, because the
line voltage is switched off.
3.
On
On
RS bit = 0
SA bit = 0
AL bit = 0
No reset, no standby active, no
alarm
The sealing process is possible.
4.
On
Off
RS bit = 0
SA bit = 0
AL bit = 1
No reset, no standby active, alarm
active
Error code 201
The line voltage is missing.
5.
On
On
RS bit = 0
SA bit = 0
AL bit = 1
no reset, no standby active, alarm
active
Error code 201
Line voltage is present, but the
alarm is not acknowledged.
6.
On
On
RS bit = 1
SA bit = 1
AL bit = 1
Reset active, standby active
(”handshake” procedure), alarm
active
Error code 201
As long as the RS bit is set to "1",
error code 201 will continue to be
displayed.
To set the AL bit to "0", acknowl-
edge the error (
7.
On
On
RS bit = 0
SA bit = 0
AL bit = 0
1
no reset, no standby active, no
alarm
The alarm is acknowledged, i. e.
the error is cleared, and reset is
completed. The controller sets the
SA bit to “0”.
The sealing process is possible.