background image

MCT88M-IO Operating Manual.doc 

  

2019-03-06 

 

8/20 

 

3EOL/NC type 

3EOL/NC input can be in normal, triggered, masking, triggered with 
masking,  tamper  (sabotage)  or  malfunction  state.  In  normal  state 
C

A

, C

B

 and C

Tamp 

contacts are closed. Input triggering is caused by 

C

contacts  opening.  C

B

  contacts  opening  is  recognized  as  the 

masking  state.  Simultaneous  opening  of  C

A

  and  C

B

  contacts  is 

recognized  as  the  triggered  with  masking  state.  C

Tamp

  contacts 

opening  is  recognized  as  the  tamper  (sabotage)  state.  Input 
shorting to the ground is recognized as the malfunction state. 
 
 
 
 
 
 
 

Fig. 12 3EOL/NC input type 

3EOL/DW/NO and 3EOL/DW/NC 

These input types are operated in the same way as 3EOL/NO 3EOL/NC input types with the exception that 
masking  state  is  interpreted  as  triggering  of  the  second  input.  In  VISO  software  DW  input  type  is 
represented by two independent inputs. Each can be used for different purpose and assigned with different 
function. 

Parametric resistors 

The same values of param

etric resistors are used for all inputs i.e. 1kΩ; 1,2kΩ; 1,5kΩ; 1,8kΩ; 2,2kΩ; 2,7kΩ; 

3,3kΩ;  3,9kΩ;  4,7kΩ;  5,6kΩ;  6,8kΩ;  8,2kΩ;  10kΩ;  12kΩ. T

amp

  resistor  defines  a  value  of  resistor  used  to 

detect  the  tamper  (sabotage)  state.  Alarm  A  resistor  defines  a  value  of  resistor  used  to  detect  triggered 
state. Alarm B resistor defines a value of resistor used to detect an additional triggering state of 3EOL/DW 
input  type  or  masking  state  of  3EOL  input  type.  Alarm  A  resistor  value  must  differ  than  value  of  Alarm  B 
resistor at least by three positions in the list above. Total resistance of wire used to connect contacts to input 
should not e

xceed 100 Ω. Default values of parametric resistors: 

  T

amp

 

= 1 kΩ 

 

Alarm A = 2,2 kΩ 

 

Alarm B = 5,6 kΩ 

Response time 

Response time parameter defines minimal impulse time on the input which triggers the input. Each input can 
be configured individually in range of 50 to 5000 ms within low level configuration (RogerVDM). 

Tamper detector 

Built-in tamper (sabotage) detector 

enables detection of unauthorized opening of device’s enclosure as well 

as  detachment  of  the  enclosure  from  wall.  The  detector  is  internally  connected  to  the  MCT88M-IO  fourth 
input. It does not require low level configuration (RogerVDM) or any additional installation arrangements but 
it is essential to mount the terminal in such way that tamper lever (fig.16) would properly press the detector 
(fig.  15).  The  detector  requires  high  level  configuration  which  consists  in  assignment  of  the  function 

[133] 

Tamper Toggle o

n the level of a 

Main Board

 of a controller in VISO software navigation tree.  

Outputs 

The  terminal  offers  2  transistor  open  collector  type  outputs  (15V/150mA  rated)  and  1  relay  output  with 
NO/NC  contacts  (30V/1.5A  DC/AC  rated).  Electric  parameters  such  as  polarity  are  configured  within  low 
level  configuration  (RogerVDM).  Function  are  assigned  to  outputs  within  high  level  configuration  (VISO). 
Multiple functions with different priorities can be assigned to the same output at the same time. 

Identification 

Following user identification methods are offered by the terminal: 

  MIFARE Ultralight/Classic/Plus/DESFire proximity cards. 

Содержание MCT88M-IO

Страница 1: ...Roger Access Control System MCT88M IO Operating Manual Product version 1 0 Firmware version 1 0 2 97 or newer Document version Rev A ...

Страница 2: ...light Classic DESFire Plus cards reader NFC and BLE mobile device identification Colour graphic display Touch keypad 4 function keys 3 parametric EOL inputs 2 transistor outputs 1 relay output RS485 interface Ethernet LAN interface Dimensions 155 5 x 85 0 21 5 Power supply The terminal requires power supply voltage in range of 11 15VDC It can be supplied from the MC16 access controller e g TML out...

Страница 3: ...r tree or any combination of them except for loop The matching resistors terminators connected at the ends of transmitting lines are not required In most cases communication works with any cable type standard telephone cable shielded or unshielded twisted pair etc but the recommended cable is unshielded twisted pair U UTP cat 5 Shielded cables should be limited to installations subject to strong e...

Страница 4: ...thin high level configuration VISO e g Set T A Mode Register Guard Tour Event Set Automation Node On etc Within low level configuration RogerVDM of the terminal it is possible configure if terminal distinguishes short and long key pressings Consequently each types of key press can be assigned with different function Display The terminal is equipped with colour display 4 lines 16 characters each Th...

Страница 5: ...ge LED indicates card reading and can signal other system functions including device malfunction Note Synchronic pulsing of all three LEDs signifies lost communication with MC16 controller Buzzer The terminal is equipped with buzzer which is used to signal integral functions and it can be additionally programmed with other available functions within high level configuration VISO Inputs The termina...

Страница 6: ...OL NO type EOL NO input can be in normal triggered or tamper sabotage state In normal state CA contacts are opened Input triggering is caused by CA contacts closing The change of RTamp resistor measured resistance in normal state indicates the tamper sabotage state Fig 7 EOL NO input type EOL NC type EOL NC input can be in normal triggered or tamper sabotage state In normal state CA contacts are c...

Страница 7: ...t triggering is caused by CA contacts opening CTamp contacts opening is recognized as the tamper sabotage state Input shorting to the ground is recognized as the malfunction state Fig 10 2EOL NC input type 3EOL NO type 3EOL NO input can be in normal triggered masking triggered with masking tamper sabotage or malfunction state In normal state CA and CB contacts are opened while CTamp contacts are c...

Страница 8: ...er than value of Alarm B resistor at least by three positions in the list above Total resistance of wire used to connect contacts to input should not exceed 100 Ω Default values of parametric resistors Tamp 1 kΩ Alarm A 2 2 kΩ Alarm B 5 6 kΩ Response time Response time parameter defines minimal impulse time on the input which triggers the input Each input can be configured individually in range of...

Страница 9: ...ndroid iOS using NFC or Bluetooth BLE communication Prior to use of BLE NFC identification on the terminal within its low level configuration see section 4 configure own NFC BLE authentication factor encryption key and NFC BLE communication encryption key while in case of Bluetooth additionally verify if the parameter BLE activated is enabled Install Roger Mobile Key RMK app on mobile device and c...

Страница 10: ...STALLATION Fig 14 Enclosure disassembly Fig 15 Internal side of the front panel Table 3 Screw terminals Screw terminal Description OUT2 OUT2 output line OUT1 OUT1 output line IN3 IN3 input line IN2 IN2 input line IN1 IN1 input line NO REL relay output NO ...

Страница 11: ...ont panel regularly by means of wet cloth and mild detergent Do not clean by means of abrasive materials and strong cleaners like alcohols solvents etc Damages to screen surface are beyond the scope of warranty 3 OPERATION SCENARIOS Access T A and building automation terminal The MCT88M IO terminal when connected to MC16 access controller can be at the same time used for access control Time Attend...

Страница 12: ...oftware and they can be made available to third party software through RACS 5 Integration Server Assets management terminal The MCT88M IO terminal when connected to virtual controller via Ethernet LAN can be used as terminal for management of assets under control of RACS 5 system Virtual controller is a Windows Service installed on computer by means of RogerSVC software which is available at www r...

Страница 13: ...atically display Configuration tab 5 Select RS485 communication interface and specify unoccupied RS485 address in range of 100 115 or select Ethernet communication interface and specify IP address Configure other low level configuration parameters as needed e g NC input type for IN1 input as for diagram in fig 17 6 Click Send to Device to update the configuration of device 7 Optionally make a back...

Страница 14: ...l Range 1 REK 2 UCE 3 UCE REK Default value 3 UCE REK Optical signalisation LED SYSTEM pulsing when card near reader Parameter enables LED SYSTEM orange pulsing when card is close to the device Range 0 No 1 Yes Default value 0 No Backlight level Parameter defines backlight level When set to 0 then backlight is disabled Range 0 100 Default value 100 Backlight dimming when card key used Parameter en...

Страница 15: ...e elapses the buffer is cleared even if card PIN is not transmitted to controller Range 1 64 Default value 10 AF type Parameter defines authentication factor type returned by terminal Default value 0010 Number 40bits Long card read time s Parameter defines long card read time When set to 0 then long read is disabled Range 0 64 Default value 0 Long key press time s Parameter defines long press time...

Страница 16: ...hich will be used to generate returned card number RCN RCN is the actual card number read by reader and it is created as sum of serial card number CSN and programmable card number PCN Programmable card number PCN settings for Mifare Ultralight Sector type Parameter defines sector type with programmable number PCN If the option 0 None is selected then card returned number RCN will include only CSN ...

Страница 17: ... 0 2 to for sectors 0 31 and 0 14 for sectors 32 39 Default value 0 Key type Parameter defines key type used to access sector with PCN Range 0 A 1 B Default value 0 A Programmable card number PCN settings for Mifare Desfire Sector type Parameter defines sector type with programmable number PCN If the option 0 None is selected then card returned number RCN will include only CSN and PCN will be disc...

Страница 18: ...s sound 6 Remove jumper from MEM contacts and restart the device High level configuration VISO The purpose of high level configuration is to define logical functioning of the terminal which communicates with the MC16 access controller and it depends on applied scenario of operation The example of access control system configuration is given in AN006 application notes which is available at www roge...

Страница 19: ... Reading range Up to 7 cm for MIFARE and NFC Up to 10 m for BLE depends on ambient conditions and particular mobile device Terminal s radio power can be increased within low level configuration Distances Up to 1200 m between controller and terminal RS485 IP Code IP41 Environmental class acc to EN 50133 1 Class I indoor general conditions temperature 5 C to 40 C relative humidity 10 to 95 no conden...

Страница 20: ... electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment Weight of the equipment is specified in the document Contact Roger sp z o o sp k 82 400 Sztum Gościszew...

Отзывы: