Note: If there is no evident need for global type functions in the PRxx2 based system, it is 
recommended not to install CPR32-SE.  

Installation 

The CPR32-SE module can be installed in any metal or plastic enclosure which guarantees adequate 
protection from dust, water and moisture. Also, enclosure should assure required temperature, 
ingress protection and security. All wirings must be made before module will be powered on. 

Note: CPR32-SE will not start operation from battery itself. It is necessary to provide AC supply to 
start module’s operation. 

All devices working in access network and connected to the same RS485 communication bus should 
share common minus (common ground). In order to assure this condition use separate wire (it can 

be a signal type one) and connect all minuses of all powers sources in the system. If required 
system supply minus can be earthed in one, arbitrary selected point. 

 

Note: It is forbidden to short positive (+) supply outputs from various devices working in the 
system. 

Содержание CPR32-SE v2.0

Страница 1: ...Roger Access Control System CPR32 SE v2 0 Access System Controller Firmware 2 06 5018 Requires PR Master v4 3 3 504 or higher Operating Manual Rev A...

Страница 2: ...ure will be lost Once the CPR operation is restored controllers will refresh their time settings and will restore full functionality Note Theoretically PRxx1 controllers can be used without CPR32 SE h...

Страница 3: ...ings must be made before module will be powered on Note CPR32 SE will not start operation from battery itself It is necessary to provide AC supply to start module s operation All devices working in ac...

Страница 4: ...ence of battery is not obligatory When installed battery provides two important features Delivers power supply in case of AC network failure Provides an extra current in periods when total current con...

Страница 5: ...d be limited to these installation where strong electrical interferences are expected The maximum distance of communication must assure two conditions The max cable run between CPR32 SE module and any...

Страница 6: ...Name Type Description 00 None None No function assigned to line 01 Clear alarm on CPR Input Triggering this input clears all alarms on CPR module 02 Tamper loop Input Triggering this input starts tamp...

Страница 7: ...ains active for 180s or can be cleared earlier from input 01 or 12 71 Alarm in system Output Line is activated when either tamper alarm or technical problem is detected Also it is triggered when Door...

Страница 8: ...is restored 84 Buffer alarm Output Line indicates that event buffer in fully occupied output remains active as long as mentioned state exists Info When buffer is full the newly coming events erase th...

Страница 9: ...they are released Roger design team continuously work on enhancements and publish them on company web site www roger pl Roger customers are advised to register at web site so company will let inform w...

Страница 10: ...6k resistor COM Input common internally shorted with supply minus GND IN2 IN2 input internally pulled up to supply plus through 5 6k resistor IN3 IN3 input internally pulled up to supply plus through...

Страница 11: ...0VA Distances Between controller and reader or extension module max 150 m Between controller and communications interface or CPR32 SE network controller 1200m Environmental class according to EN 50131...

Страница 12: ...o four PR402 boards into single ME 2 enclosure also suitable for extension modules and CPR32 SE RM 2 Relay module with plastic enclosure the RM 2 offers two relays with one NO NC contact 1 5A 24V rate...

Отзывы: