Charging current adjustment 

When required, battery charging current can be adjusted in 100-500mA range. In order to set 
required charging current connect battery (which is partly discharged) to CPR32-SE and then using 

screwdriver rotate POT1 potentiometer and observe current which flow into battery. Charging 
current should be observed using multimeter connected in series with battery plus or minus. 

Note: It is forbidden to set battery charging current below 100mA level because in this case 
charging current is not guaranteed. 

RS485 communication bus 

The RS485 serial communications interface in CPR32-SE consist of three terminals: A, B and SHLD.  
The A and B are signal line while SHLD is used to connect cable’s shield (if used). Electrically, 

communication bus standard represents RS485 however there are two important modification in  
respect to typical RS485: 

 

Daisy chain structure is not obligatory (free topology is allowed) 

 

Terminating resistors on both ends of bus are not required 

 

Any type of signal cable is accepted 

Generally, free topology of communication bus is allowed, comm. bus cables can form “three’’, “star” 

or any combination of them however closed loops are forbidden. It is recommended to use UTP 
cable for A and B lines nevertheless any type of signal cables is accepted as well. The use of 

shielded cables should be limited to these installation where strong electrical interferences are 
expected.  
The maximum distance of communication must assure two conditions: 

 

The max. cable run between CPR32-SE module and any access controller or communication 

interface must not exceed 1200m 

 

The max. cable run between communication interface and any access controller or CPR32-SE 
module communication interface must not exceed 1200m 

For longer communication distances it is possible to use UT-3 or UT-4 interfaces. Using two UT-3 
units communication distances can be extended by next 1200m, while for UT-4 distance is not 
limited because it uses computer network.  

Inputs 

CPR32-SE offers four programmable inputs (IN1, IN2, IN3 and IN4). All of them have the same 
electric structure and can be configured as NO or NC. Each input is internally biased to supply plus 

(+12V) through 5.6k

 resistor, this makes that +12V is observed on the not connected (floating) 

input.  
The NO type input goes active when shorted to supply minus (GND), if input is left unconnected or 

shorted to +12V it represents passive (normal) state. 
The NC line in passive (normal) state should be connected to supply minus (GND), it becomes active 
(triggered) when connection with GND is discontinued. If input is left unconnected or shorted to 

+12V it is in active (triggered) state. 

Note: If required, inputs can be connected together - still they can be programmed to different 
functions. 

Relay outputs 

CPR32-SE has two, programmable,  relay outputs (REL1 and REL2). Each of them offers one 
NO/NC/COM contact rated 24V/1.5A with built-in voltage surge protection.  

Содержание CPR32-SE v2.0

Страница 1: ...Roger Access Control System CPR32 SE v2 0 Access System Controller Firmware 2 06 5018 Requires PR Master v4 3 3 504 or higher Operating Manual Rev A...

Страница 2: ...ure will be lost Once the CPR operation is restored controllers will refresh their time settings and will restore full functionality Note Theoretically PRxx1 controllers can be used without CPR32 SE h...

Страница 3: ...ings must be made before module will be powered on Note CPR32 SE will not start operation from battery itself It is necessary to provide AC supply to start module s operation All devices working in ac...

Страница 4: ...ence of battery is not obligatory When installed battery provides two important features Delivers power supply in case of AC network failure Provides an extra current in periods when total current con...

Страница 5: ...d be limited to these installation where strong electrical interferences are expected The maximum distance of communication must assure two conditions The max cable run between CPR32 SE module and any...

Страница 6: ...Name Type Description 00 None None No function assigned to line 01 Clear alarm on CPR Input Triggering this input clears all alarms on CPR module 02 Tamper loop Input Triggering this input starts tamp...

Страница 7: ...ains active for 180s or can be cleared earlier from input 01 or 12 71 Alarm in system Output Line is activated when either tamper alarm or technical problem is detected Also it is triggered when Door...

Страница 8: ...is restored 84 Buffer alarm Output Line indicates that event buffer in fully occupied output remains active as long as mentioned state exists Info When buffer is full the newly coming events erase th...

Страница 9: ...they are released Roger design team continuously work on enhancements and publish them on company web site www roger pl Roger customers are advised to register at web site so company will let inform w...

Страница 10: ...6k resistor COM Input common internally shorted with supply minus GND IN2 IN2 input internally pulled up to supply plus through 5 6k resistor IN3 IN3 input internally pulled up to supply plus through...

Страница 11: ...0VA Distances Between controller and reader or extension module max 150 m Between controller and communications interface or CPR32 SE network controller 1200m Environmental class according to EN 50131...

Страница 12: ...o four PR402 boards into single ME 2 enclosure also suitable for extension modules and CPR32 SE RM 2 Relay module with plastic enclosure the RM 2 offers two relays with one NO NC contact 1 5A 24V rate...

Отзывы: