RODIX Inc. 

 

CE notes about voltage fluctuations and flicker 

 
What you need to know about the CE voltage fluctuations and flicker standard: 

For machines that have the CE mark, one of the many standards that machine must conform to is the Limitation of 
voltage fluctuations and flicker.  The machine configuration will determine when to apply this standard. 

 
International Standard IEC 61000-3-3

 Effective 

1/1/2001 

“Limits – Limitation of voltage fluctuations and flicker in low-voltage supply systems for equipment with rated 
current 

 16 amps per phase.”  This part of IEC 61000 deals with the limitation of voltage fluctuations and flicker 

injected into the public low-voltage supply system (electric utility).  When the amperage is over 16 amps, a 
companion standard, IEC 6100-3-11 is applied.  
 
 The limits in this standard are based mainly on the subjective severity of how much a 230V/60 W light bulb flickers 
when the supply voltage fluctuates.  The frequent flickering of a light bulb can adversely affect some people. 
 

When the standard does not apply:  

This standard doesn’t apply if the 230V machine is powered by a step down transformer.   
 
The scope of the standard states: 
IEC 61000-3-3 is applicable to electrical and electronic equipment having an input current up to and including 16A 
per phase, and intended to be connected to public low-voltage distribution systems of between 220V and 250V at 
50Hz line to neutral.   

 

Public low-voltage distribution systems are power supply systems allowing the direct connection of equipment with 
rated voltages between 200 and 260V (single phase) or between 340 and 450V (phase to phase).  Higher voltage 
distribution systems, which are connected to power substations, are not considered to be public low-voltage systems. 

 

A 230V machine with a vibratory feeder is typically powered by a step down transformer that is installed in a 
factory.  Thus the machine is powered by a higher voltage distribution system that is not directly connected to the 
230V public low-voltage system.  Because of this, the machine is outside the scope of the standard

1

.  A machine that 

is connected to 60Hz power is also outside the scope of the standard. 
 

When the standard does apply:  

The standard is applicable when a 230V machine is powered directly from the 230V public low-voltage supply 
system.   

 

The vendor that supplies the finished machine is responsible for compliance to the applicable CE standards, not the 
end user.   This vendor is responsible for performing the compliance testing on the finished machine.   

 

Please note that EN61000-3-3 applies to 230V equipment.  There are no limits for 120V equipment since these 
limits have not yet been defined; however, in Europe the 120V equipment will be connected to a step down 
transformer that might connect to the public 230V power mains.  This means that 120V equipment that does not 
meet the standard may cause a step down transformer that connects to the public 230V to fail to meet the standard. 
 

What causes voltage fluctuations: 

When an electrical load is turned on, it can cause the supply voltage to decrease a little bit due to the resistance and 
the inductance of the supply wires and step down transformer.  The addition of a larger amp load causes a larger 
change to the supply voltage than a small amp load does.  When the load turns off, the supply voltage rebounds back 
to the original value. 
 

Disclaimer: 

Standard EN61000-3-3 applies to the vibratory feeder system, and it does not apply to the vibratory feeder control.  
The amount of voltage fluctuations and flicker depends on how often the electrical load is turned On and Off by the 
machine and how large the load is. 
 

                                                            

1

 From TUV Rheinland, FAQ 

http://www.jpn.tuv.com/en/services/product_testing/all_types_of_products/electromagnetic_compatibility_services_emc_/emc_faq.php

 

 

   

© RODIX Inc. 2006 

E:\Eng\CE\CE Flicker 060511.doc

 

Содержание 121-500-0750

Страница 1: ...1 240V Rodix No 123 294 Fuse quan 1 8 A 250V Rodix No 106 20 Littelfuse 0214008 Fuse Holder quan 1 20 A 250V Rodix No 106 17 Littelfuse03540901ZXGY Triac quan 1 Rodix No 115 32 STMicro BTA40 600B LF...

Страница 2: ...must be provided by the user A power plug socket combination can be utilized for this purpose The plug and socket must have a breaking capacity of at least the amperage of the vibratory feeder s 2006...

Страница 3: ...ONTROL A Run Jumper has been installed at the factory as shown on the enclosed wiring diagram Remote OFF ON operation of the CE 40 Plus Series Feeder Cube control can be configured to operate in one o...

Страница 4: ...ns and fax any needed information To return a control for IN or OUT of warranty service please ship it prepaid to Rodix Inc ATTN Repair Department If under warranty Rodix will repair or replace your c...

Страница 5: ...l 14 AWG Lt Bu 14 AWG Bl 14 AWG 240 VAC Gr Yl 14 AWG Bl 11 4 50 60 Hz Gn Yl COM HOT 20VK1 1 2 LINE FILTER Lt Bu PE Customer Supplied Disconnect Device PE 2 1 13 10 8 EU WIRING 11 INPUT INTERLOCK 6 8 8...

Страница 6: ...ns for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock input or AUX output The shield drai...

Страница 7: ...performed by Rodix at L F Research 12790 Route 76 Poplar Grove IL 61065 Machine Description Vibratory Feeder Control Makes CE 41 Plus CE 41H Plus CE 43 Plus CE 43H Plus CE 48 CE 48 Plus CE 48H Plus C...

Страница 8: ...he standard 1 When the standard does apply When a 230V machine is not powered by a step down transformer there should not be a problem meeting this standard if all the vibratory feeders on one machine...

Страница 9: ...down transformer that is installed in a factory Thus the machine is powered by a higher voltage distribution system that is not directly connected to the 230V public low voltage system Because of thi...

Страница 10: ...ether if they always start and stop at the same time Actual testing may prove that the number of On Off cycles shown in the chart can nearly be doubled when the Soft Start pot is adjusted for a one se...

Отзывы: