CE-48 

Plus

 

P/N 121-500-0750 

 

PRODUCT DESCRIPTION 

 

This device is used to control the vibration level a 
vibratory feeder.  The unit is powered from the incoming 
line connection. The unit has its own Master Control PC 
board.  The setup and operation is detailed in the 
following product literature. 

 

SPECIFICATIONS 

 

Line Voltage: 

 

 

230 VAC +/-10% 

Line 

Frequency: 

  50/60 

Hz 

Current:         

 

 

8A 

Output 

Voltage: 

  0-230 

VAC 

Handling & Transp. Temp. 

-40 – 60 

Operating Temp. 

 

0 – 40 

 

INSTALLATION 

 

The control is to be firmly mounted to a non-vibrating 
surface.  The control is designed to withstand conditions 
equal to IP54.  Do not install the control in a more 
severe environment.  Connections to external conduits 
or cords are to be made with hardware that is rated at 
IP54 or better.   

 

Refer to the electrical wiring diagram.  Line and load 
wiring is to be brought into the box via customer-drilled 
holes.  Use 1.5mm

2

 (#16 AWG) Mains supply wires or 

larger.  Use 1.5mm

2

 (#16AWG) load wires or larger.  

The Mains supply wires should be fused by the 
Customer at 8 amps or less.  After the wiring has been 
completed, verify the continuity of the ground bond 
connection to the control. 

 

This control is for industrial use.  Use in residential 
areas may cause interference, and in that case, special 
measures may have to be taken by the user regarding 
emissions. 

IMPORTANT - The vibratory feeder must be tuned 
to match the power line frequency of the 
destination country (50 or 60 Hz).  A feeder tuned 
to the wrong frequency will not feed parts.  The 
Rodix control operates on 50 or 60 Hz.

 

 

SAFETY 

 
When installing this control, a power supply 
disconnect device must be provided by the user.  
 A power plug/socket combination can be utilized for 
this purpose.  The plug and socket must have a 
breaking capacity of at least the amperage of the 
vibratory feeder(s). 

 

© 

2006 Hazard Communication Systems, LLC  

 

Figure 1 – Warning label installed on the control 

 

Warning – There is hazardous voltage inside the 
control.  Disconnect power before opening the 
enclosure.

  Only skilled or instructed persons should 

open the enclosure. 

 

An electrically instructed person is a person 
adequately advised or supervised by an electrically 
skilled person to enable him or her to perceive risks 
and to avoid hazards which electricity can create.  

 

An Emergency stop device must be installed on the 
machine that incorporates the CE feeder control. 

 

When the machine is installed, verify the continuity of 
the protective bonding circuit (earth ground) to the 
control.   

 

 

PERIODIC INSPECTION AND FUNCTIONAL 

TESTING 

 

When the control is operating normally, the output 
can be smoothly adjusted from zero to maximum 
by the main control knob.  If part sensors are used, 
the control starts and stops automatically 
according to the time delay settings on the circuit 
board.  If soft-start is used, the output should start 
at zero and ramp up to the desired setting each 
time the control automatically starts. 

 

The control should be kept reasonably free from 
dirt and contaminants that might inhibit proper 
cooling.  No other planned maintenance is 
necessary. 

 

Maintenance 

 

Normally no maintenance is needed for this 
control.  If troubleshooting assistance is needed, 
either visit our web site at www.rodix.com, call 
RODIX: (international call) 815-316-4700x322 or 
(USA) 1-800-562-1868x322,  FAX: 815-316-4701, 
or e-mail: 

[email protected]

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

CE-48 Plus 24-211.doc 2/27/2013 Page 1

RODIX INC. 

FEEDER CUBE

 

CE-40 

Plus Series

 

 

Содержание 121-500-0750

Страница 1: ...1 240V Rodix No 123 294 Fuse quan 1 8 A 250V Rodix No 106 20 Littelfuse 0214008 Fuse Holder quan 1 20 A 250V Rodix No 106 17 Littelfuse03540901ZXGY Triac quan 1 Rodix No 115 32 STMicro BTA40 600B LF...

Страница 2: ...must be provided by the user A power plug socket combination can be utilized for this purpose The plug and socket must have a breaking capacity of at least the amperage of the vibratory feeder s 2006...

Страница 3: ...ONTROL A Run Jumper has been installed at the factory as shown on the enclosed wiring diagram Remote OFF ON operation of the CE 40 Plus Series Feeder Cube control can be configured to operate in one o...

Страница 4: ...ns and fax any needed information To return a control for IN or OUT of warranty service please ship it prepaid to Rodix Inc ATTN Repair Department If under warranty Rodix will repair or replace your c...

Страница 5: ...l 14 AWG Lt Bu 14 AWG Bl 14 AWG 240 VAC Gr Yl 14 AWG Bl 11 4 50 60 Hz Gn Yl COM HOT 20VK1 1 2 LINE FILTER Lt Bu PE Customer Supplied Disconnect Device PE 2 1 13 10 8 EU WIRING 11 INPUT INTERLOCK 6 8 8...

Страница 6: ...ns for Electrical Noise 1 Use shielded wires for all I O Input Output signals The I O signals may include 4 20mA input Run input Sensor input 0 5VDC input Interlock input or AUX output The shield drai...

Страница 7: ...performed by Rodix at L F Research 12790 Route 76 Poplar Grove IL 61065 Machine Description Vibratory Feeder Control Makes CE 41 Plus CE 41H Plus CE 43 Plus CE 43H Plus CE 48 CE 48 Plus CE 48H Plus C...

Страница 8: ...he standard 1 When the standard does apply When a 230V machine is not powered by a step down transformer there should not be a problem meeting this standard if all the vibratory feeders on one machine...

Страница 9: ...down transformer that is installed in a factory Thus the machine is powered by a higher voltage distribution system that is not directly connected to the 230V public low voltage system Because of thi...

Страница 10: ...ether if they always start and stop at the same time Actual testing may prove that the number of On Off cycles shown in the chart can nearly be doubled when the Soft Start pot is adjusted for a one se...

Отзывы: