background image

 

  1

WJISKOOT™ MEASUREMENT SYSTEMS 

InSpec Remote I/O HUB 
(ATEX, IECEx) 

Installation, Operation & Maintenance Manual  

 

 

Manual No. H112, Rev. 2

     MEASUREMENT 

Содержание Sensia Jiskoot InSpec Remote I/O HUB

Страница 1: ...1 WJISKOOT MEASUREMENT SYSTEMS InSpec Remote I O HUB ATEX IECEx Installation Operation Maintenance Manual Manual No H112 Rev 2 MEASUREMENT...

Страница 2: ...2...

Страница 3: ...amaging electronic circuits Disposal Monitoring and Control Instruments accessories and their packaging should be sorted for environmental friendly recycling Only for EC countries Do not dispose of Mo...

Страница 4: ...lary Power DC 15 Signals 16 Relay Circuits Outputs 16 RIO DIO Module Connections Digital I O 17 RIO PUL Module Connections Pulse Inputs 18 RIO ANI Module Connections Analogue Inputs 19 RIO ANO Module...

Страница 5: ...4 Other Spares 35 Abbreviations Acronyms 36 Abbreviations Acronyms 36 Appendix A Publisher Notes 39 Support 39 Warranty 39 Disclaimer 39 Contact us 40 CERTIFIED PRODUCT Scheduled Document No modificat...

Страница 6: ...ed do not connect hazardous voltages to the instrument The following operations should only be carried out on a disconnected unit and under ESD safe conditions General mounting connection and disconne...

Страница 7: ...tely or as part of a system for integration into a larger installation Depending on the model purchased the following functions may be integrated into the unit Load Cell Amplifiers 2 off to interface...

Страница 8: ...x E ETL Listed USA Canada AC DC PSUs X None fitted A Ancillary AC DC PSU Module Transmitter Power B Ancillary AC DC PSU Solenoid Power C Both Module Ancillary Power Relays X None 0 to F AC or DC Outpu...

Страница 9: ...red unit With Intrinsically Safe Isolators Model Numbers A 3 B 3 A 4 B 4 A 5 B 5 C 3 C 4 C 5 AC powered unit Without Intrinsically Safe Isolators Model Numbers A X B X C X DC powered unit With Intrins...

Страница 10: ...sconnect the equipment from the supply It must be located nearby easily reached and marked as the disconnecting device for the equipment ENCLOSURE MOUNTING ORIENTATION POSITION LIFTING CAUTION This eq...

Страница 11: ...ping lugs Terminal block screws must be tightened to a torque of 4 4 to 5 3 lb in The hazardous area end of any unused cores shall be either a connected to earth or b adequately insulated by means of...

Страница 12: ...equal to the marking on the enclosure II 2 G Ex db IIB H2 Gb or better when a thread adapter is used When changing the size of an entry this should be documented and marked accordingly per IEC EN 6007...

Страница 13: ...ective Earth PE connection point 13 Section 4 Relay Circuits Outputs Yes Relay Output No 1 14 13 Relay Output No 2 14 13 Relay Output No 3 14 13 Relay Output No 4 14 E Section 4 Earthing Requirements...

Страница 14: ...then the screen should be terminated at the source end If both the signal source and signal inputs are both grounded terminating the screen at both ends is not recommended as this may reduce the perfo...

Страница 15: ...e or circuit breaker and cabling are suitably sized ANCILLARY POWER DC 24VDC 32 Watts max Model Numbers B C An optional AC DC PSU intended to supply equipment such as solenoid coils TERMINAL FUSE DUTY...

Страница 16: ...C DC AC A DC AC DC AC 3 AC AC DC DC B DC AC DC DC 4 AC DC AC AC C DC DC AC AC 5 AC DC AC DC D DC DC AC DC 6 AC DC DC AC E DC DC DC AC 7 AC DC DC DC F DC DC DC DC X No relays fitted Terminals 11 13 and...

Страница 17: ...module please refer to the InSpec Remote I O Module manual The main field terminal assignments are as follows RIO DIO MODULE FIELD CONNECTIONS TERMINAL DUTY 1 24VDC Common Connection Points From Exte...

Страница 18: ...information about the RIO PUL module please refer to the InSpec Remote I O Module manual The main field terminal assignments are as follows RIO PUL MODULE FIELD CONNECTIONS TERMINAL DUTY 1 Ch 1 Pulse...

Страница 19: ...or complete information about the RIO ANI module please refer to the InSpec Remote I O Module manual The main field terminal assignments are as follows RIO ANI MODULE FIELD CONNECTIONS TERMINAL DUTY 1...

Страница 20: ...complete information about the RIO ANO module please refer to the InSpec Remote I O Module manual The main field terminal assignments are as follows RIO ANO MODULE FIELD CONNECTIONS TERMINAL DUTY 1 Ch...

Страница 21: ...x Ii Imax Pi Pi are not exceeded by the safety parameters Uo Voc Io Isc Po Po of the D5264 D5030D series Associated Apparatus connected to it Also consider the maximum operating temperature of the fie...

Страница 22: ...of Co and Lo parameters are applicable and shall not be exceeded 50 of the Co and Lo become the limits which must include the cable such that Ci device C cable 50 of Co and Li device L cable 50 of Lo...

Страница 23: ...e the associated stopping boxes shall be installed immediately at the enclosure Unused openings for cable or conduit entries shall be closed with blanking elements suitable for the relevant type of pr...

Страница 24: ...InSpec Remote I O HUB ATEX IECEx 24 Use The unit shall only be operated as intended and only in undamaged and perfect condition and only within the environmental and electrical constraints stated with...

Страница 25: ...refer to the product GM Int handbooks for calibration instructions for the following o Load Cell Amplifier Calibration GM Int D5264S Modules If fitted o Can High Isolating Converter Adjustment GM Int...

Страница 26: ...ircuits as defined in Section 15 Instrument power should be connected via a suitable power disconnect using a suitably sized and electrically and mechanically protected cable Always replace fuses with...

Страница 27: ...itude 2000 metres max 6562 feet Power Supply Voltage Frequency AC Powered 100 to 240 V AC 50 60 Hz DC Powered 24V DC 10 Power Consumption AC Powered 80 Watts Max All options fitted DC Powered 30 Watts...

Страница 28: ...s IEC EN 60079 1 Explosive atmospheres Part 1 Equipment protection by flameproof enclosures d IEC EN 60079 11 Explosive atmospheres Part 11 Equipment protection by intrinsic safety i Models 3 4 or 5 I...

Страница 29: ...d from the InSpec Enhanced Controller using Modbus TCP protocol COMMUNICATIONS FAILURE WARNING In the event of a communications failure to the RIO module s the modules will assume a known state It is...

Страница 30: ...y the site operator s health and safety systems ANNUAL MAINTENANCE It is recommended that the Jiskoot InSpec Remote I O Hub is calibrated and a detailed inspection of the equipment carried out at leas...

Страница 31: ...ted as intended and only in undamaged and perfect condition ATTENTION Caution Handle electronic components and printed circuit card assemblies only when you are properly grounded in an ESD Protected A...

Страница 32: ...Section 12 Product Specific Drawings InSpec Remote I O HUB ATEX IECEx 32 Product Specific Drawings Please refer to the project specific documentation package...

Страница 33: ...erminal rail is good and of the correct size and type Section 14 Spare Fuses AC or DC powered units Check that the green status LED on each Jiskoot RIO xxx Module is flashing The RIO xxx Modules have...

Страница 34: ...se sizes that may be fitted to the unit are listed below REMOTE I O HUB MODEL NUMBER FUSE ID FUSE TYPE DUTY SENSIA PART A B C F1 T2AH250V 5x20mm Main AC Supply Fuse 3J 28 0050 00 A B C F2 T1AH250V 5x2...

Страница 35: ...DC Load Crydom CN024D24 3J 29 0086 00 Solid State Relay for AC Load Crydom CN240A24 3J 29 0087 00 1 2 3 4 InSpec Digital I O Module Sensia RIO DIO 3J 43 0240 00 1 2 3 4 InSpec Pulse Input Module Sensi...

Страница 36: ...ases that may produce a reduction of dielectric strength or surface resistivity PSU Power Supply Unit PTC Positive Temperature Coefficient SELV Safety Extra Low Voltage circuit An SELV circuit is defi...

Страница 37: ...InSpec Remote I O HUB ATEX IECEx 37 Page Left Intentionally Blank...

Страница 38: ...InSpec Remote I O HUB ATEX IECEx 38 Page Left Intentionally Blank...

Страница 39: ...ch products software supplies or materials on their return to Seller or at Seller s option to the allowance to the customer of credit for the cost of such items In no event shall Seller be liable for...