38
Operation
Drive operation
Chassis drive operation
POWER ON start
SPEED REFERENCE: External signal or potentiometer
START/STOP control: POWER ON/OFF
IMPORTANT:
It is necessary to wire a jumper between B1
and B3 if no START/STOP switches are to be used.
IMPORTANT:
Line starting and line stopping (applying and
removing AC line voltage) is recommended for infrequent
starting and stopping of a drive only. When AC line voltage
is applied to the drive, the motor accelerates to the speed
set by the speed adjust potentiometer or analog input
signal. When AC line voltage is removed, the motor coasts
to a stop.
1.
Turn the speed adjust potentiometer full
counterclockwise (CCW), or set the external reference
signal so that it is at its lowest level (0V or 4 mA).
2.
Apply AC line voltage.
Содержание RELIANCE ELECTRIC DC3N Series