Problem
Possible
Causes
Suggested
Solutions
Troubleshooting
Line fuse does
not blow, but
motor does not
run
1. Speed adjust
potentiometer,
voltage external
reference signal,
or current
external
reference signal
set to zero
speed.
2. Speed adjust
potentiometer,
voltage or
current external
reference signal
not connected to
drive input
properly;
connections are
open.
3. S2 is shorted to
S1.
1. Increase the
speed adjust
potentiometer,
voltage, or
current setting.
2. Check
connections
to input. Verify
that connections
are not open.
3. Remove short.