21
START/STOP pushbuttons
Installation
Pushbutton operation of the DC3N drive requires that a
(momentarily) normally-closed STOP pushbutton be wired
to terminals B2 and B3 and a (momentarily) normally-open
START pushbutton wired to terminals B1 and B2. These
pushbuttons must be used together and are not included
with the drive. The B1, B2 and B3 terminals are on terminal
block 502 (TB502).
IMPORTANT:
If the START/STOP pushbuttons are not
used, wire a jumper between terminals B1 and B3 to
bypass the latching circuit. The drive will then operate in a
power-up start mode. See Figure 6 (page 23) for these
switch connections.
ATTENTION:
Starting and stopping with the start/stop
terminals does not disconnect AC power in the stop
position. A hardwired AC power disconnection switch
must be mounted between the AC source and
terminals L I and L2. This is required, as the DC3
drive does not have an armature loop contactor. A
single fault like a power device short may cause
motor rotation when in the stop mode. The user is
responsible for assuring safe conditions for operating
personnel by providing suitable guards, audio or
visual alarms, or other devices. Failure to observe
these precautions could result in bodily injury.