Publication CNET-IN002A-EN-P - December 2001
2-14
Plan a ControlNet Coax Media System
•
Avoid connecting a single node’s redundant trunk cable
connections on different segments; this will cause erratic
operation.
A node supporting redundant trunk-cable connections will function
even if trunk cable A is connected to the B connector on the node
and vice-versa. This makes cable fault indications (on the hardware
or in software) difficult to interpret and makes locating a bad cable
segment very difficult.
trunk cable A =
trunk cable B =
20135-m
node
1
node
1
node
1
1
Node supporting redundant media
trunk cable A =
node
1
terminator
terminator
terminator
terminator
SEGMENT
SEGMENT
repeater
repeater
trunk cable B =
SEGMENT
SEGMENT
trunk cable A =
trunk cable B =
node
1
node
1
node
1
1
Node supporting redundant media
trunk cable A =
trunk cable B =
terminator
terminator
terminator
terminator
20136-m
repeater
repeater