1-14
Wire/Cable Types
standard and are appropriate for the environment. Cables should also meet
TIA/EIA standards at industrial temperatures.
Shielded cable is always recommended when the installation may include
welding, electrostatic processes, drives over 10 hp, Motor Control Centers,
high power RF radiation or devices carrying current in excess of 100 Amps.
Shield handling and single point grounding, also discussed in this
document, play an extremely important role in the proper operation of
Ethernet installations.
Finally, there are distance and routing limitations published in detail.
Remote I/O and Data Highway Plus (DH+)
Only 1770-CD, Belden #9463 is tested and approved for Remote I/O and
DH+ installations.
The maximum cable length depends on the chosen baud rate:
All three connections (blue, shield and clear) must be connected at each
node.
Do not connect in star topology. Only two cables may be connected at any
wiring point. Use either series or daisy chain topology at all points.
Serial (RS232 /485)
Standard practices for serial communications wiring should be followed.
Belden 3106A or equivalent is recommended for RS232. It contains one
twisted pair and 1 signal common. Recommended cable for RS485 is 2
twisted pair with each pair individually shielded.
Baud Rate
Maximum Cable Length
57.6 KBPS
3,048 m (10,000 ft.)
115.2 KBPS
1524 m (5000 ft.)
230.4 KBPS
762 m (2500 ft.)
Содержание Allen-Bradley 1305-AA02A
Страница 1: ...Installation Instructions Wiring and Grounding Guidelines for Pulse Width Modulated PWM AC Drives ...
Страница 4: ...ii Summary of Changes Notes ...
Страница 40: ...2 18 Power Distribution Notes ...
Страница 48: ...3 8 Grounding Notes ...
Страница 68: ...4 20 Practices Notes ...
Страница 78: ...6 8 Electromagnetic Interference Notes ...
Страница 94: ...Glossary 4 UL Underwriters Laboratories ...
Страница 100: ...Index 6 ...
Страница 101: ......