Power Distribution
Transformer Impedance (in ohms)
Transformer Impedance (in ohms)
Example: The drive is rated 1 Hp, 480V, 2.7A input.
The supply transformer is rated 50,000 VA (50 kVA), 5% impedance.
Note that the percent (%) impedance has to be in per unit (5% becomes
0.05) for the formula.
0.22% is less than 0.5%. Therefore, this transformer is too big for the drive
and a line reactor should be added.
Z
xfmr
V
line
line
–
3
I
xfmr
rated
–
⋅
----------------------------------------
⋅
% Impedance
=
% Impedance is the nameplate impedance of the transformer
Typical values range from 0.03 (3%) to 0.06 (6%)
Z
xfmr
(V
line
line
–
VA
----------------------------------------
⋅
% Impedance
=
)
2
or
Z
xfmr
V
line
line
–
3
I
xfmr
rated
–
⋅
----------------------------------------
⋅
% Impedance
=
% Impedance is the nameplate impedance of the transformer
Typical values range from 0.03 (3%) to 0.06 (6%)
ohms
102.6
7
.
2
3
480V
I
3
V
Z
rating
input
line
-
line
drive
=
=
=
Ohms
0.2304
05
.
0
000
,
50
480
Impedance
%
.
)
(V
=
Z
2
2
line
-
line
xfrmr
=
.
=
VA
%
0.22
0.00224
102.6
0.2304
Z
Z
drive
xfrmr
=
=
=