4-4
Practices
Figure 4.3 Bolt Mounting of Ground Bus or Chassis to Back Panel
If the drive chassis does not lay flat before the nuts / bolts are tightened, use
additional washers as shims so that the chassis does not bend when you
tighten the nuts.
Conduit Entry
Entry Plates
In most cases, the conduit entry plate will be a paint-free conductive
material. The surface of the plate should be clean of oil or contaminants. If
the plate is painted, use a connector that cuts through the paint and makes a
high quality connection to the plate material
Or
Remove the paint around the holes to the bare metal one inch in from the
edge of the plate. Grind down the paint on the top and bottom surfaces. Use
a high quality joint compound when reassembling to avoid corrosion.
Back Panel
Bolt
Paint Free Area
Nut
Flat Washer
Mounting Bracket
or Ground Bus
Star Washer
If mounting bracket is coated with a
non-conductive material (anodized,
painted, etc.), scrape the material off
around the mounting hole.
Star Washer
Nut
Flat Washer
Star Washer