4-12
Practices
Figure 4.10 Proper Cabinet Ground - Drives & Susceptible Equipment
Within Conduit
Do not route more than 3 sets of motor leads (3 drives) in the same conduit.
Maintain fill rates per applicable electrical codes.
Do not
run power or
motor cables and control or communications cables in the same conduit. If
possible, avoid running incoming power leads and motor leads in the same
conduit for long runs.
Loops, Antennas and Noise
When routing signal or communications wires, avoid routes that produce
loops. Wires that form a loop can form an efficient antenna. Antennas work
well in both receive and transmit modes, these loops can be responsible for
noise received into the system and noise radiated from the system. Run feed
and return wires together rather than allow a loop to form. Twisting the pair
R S T PE
U V W PE
U V W PE
Incoming Power
Conduit / Armor
Common Mode
Current on Armor
or Conduit
Output Conduit or Armor
(Bonded to Cabinet)
Common Mode Current on
Cabinet Backplane / Subpanel
Cabinet
Backplane / Subpanel