Rockwell Automation Publication 2198-RM005A-EN-P - October 2020
15
Replacement Considerations Chapter 1
Continuous output power
@ 110V nom single-phase
@ 230V nom single-phase
@ 230V nom three-phase
0.22 kW
0.46 kW
0.72 kW
0.36 kW
0.76 kW
1.18 kW
0.67 kW
1.41 kW
2.18 kW
0.97 kW
2.02 kW
3.13 kW
Internal shunt on
387.5V
Internal shunt off
377.5V
Internal shunt resistor
100 Ω
100 Ω
60 Ω
60 Ω
Internal shunt power
30 W
30 W
50 W
50 W
Bus undervoltage limit
72V @110V AC input
144V @230V AC input
Bus overvoltage limit
405V
Bus capacitance
330 µF
560 µF
660 µF
1120 µF
Capacitive energy absorption
@ 110V nom AC input
@ 230V nom AC input
21.31 J
5.94 J
36.17 J
10.08 J
42.63 J
11.88 J
72.34 J
20.16 J
Efficiency
91% @110V (single-phase) AC input
95% @230V (single-phase) AC input
97% @230V (three-phase) AC input
Short-circuit current rating
(5)
200,000 A (rms) symmetrical
(1)
Drives are limited to one power cycle per minute.
(2) The cooling fan runs as part of the control power startup routine, when the inverter is enabled, and if the inverter temperature exceeds preset threshold.
(3) For current values when motors include a holding brake, refer to Kinetix Servo Drive Specifications Technical Data, publication
(4) Peak RMS current allowed for up to 1.0 seconds.
(5) This rating is only valid if UL specified fuses are used.
Table 11 - Kinetix 5300 (110V and 230V, single-phase and three-phase) Power Specifications (continued)
Attribute
2198-C1004-ERS
2198-C1007-ERS
2198-C1015-ERS
2198-C1020-ERS
Table 12 - Kinetix 5300 (230V, three-phase) Input Power Specifications
Attribute
2198-C2030-ERS
2198-C2055-ERS
2198-C2075-ERS
AC input voltage
170…253V rms, three-phase (230V nom)
AC input frequency
47…63 Hz
Main AC input current (rms)
(1)
15.18 A
31.13 A
36.93 A
Max inrush current (0-pk)
7.4 A
14.8 A
14.8 A
Peak AC input current (rms)
41.26 A
73.06 A
86.25 A
Control power input voltage
(2)
21.6…26.4V DC
24V DC nom
Control power input current
(3)
(non-brake motors)
0.9 A
DC
1.7 A
DC
1.7 A
DC
Continuous output current (rms)
19.6 A
40.2 A
47.7 A
Continuous output current (0-pk)
27.7 A
56.9 A
67.5 A
Peak output current (rms)
(4)
61.0 A
108.0 A
127.5 A
Peak output current (0-pk)
86.3 A
152.7 A
180.3 A
Line loss ride through
20 ms
Continuous output power
5.02 kW
10.30 kW
12.22 kW
Internal shunt on
387.5V
Internal shunt off
377.5V
Internal shunt resistor
60 Ω
40 Ω
Internal shunt power
50 W
75 W
Bus undervoltage limit
144V
Bus overvoltage limit
405V
Bus capacitance
1680 µF
2460 µF
3280 µF
Capacitive energy absorption
30.25 J
44.29 J
59.05 J
Efficiency
97%
Short-circuit current rating
(5)
200,000 A (rms) symmetrical
(1)
Drives are limited to one power cycle per minute.
(2) The cooling fan runs as part of the control power startup routine, when the inverter is enabled, and if the inverter temperature exceeds preset threshold.
(3) For current values when motors include a holding brake, refer to Kinetix Servo Drive Specifications Technical Data, publication
(4) Peak RMS current allowed for up to 1.0 seconds.
(5) This rating is only valid if UL specified fuses are used.