MICON 500C Electronic Sequencing
30
234AY00.INS R06
Computer Installation Guide
7.1.5.2
FILL OPTION 2 (CONT’D)
At the start of the sale, the main valve is opened and the motor actuator is advanced to the high bank
position. When flow starts and the optional
pfs
initialization has completed, the flow continues with only
the main solenoid valve open. The flow will be allowed to stabilize for 2 seconds. Flow will continue
until the IPTP1 or the MIN. FLOW is reached; then the motor actuator will advance to activate the mid
bank line. Once again the flow rate will be allowed to stabilize for 2 seconds. Flow will continue until
IPTP2 or the MIN. FLOW has been reached, then the motor actuator will be advanced to the high bank
line position.
Flow will continue until the end of sale (flow rate below the MIN. FLOW level), when the main flow
solenoid will be closed and the motor actuator valve returns to the home position.
Alarm output is disabled with this fill option.
Motor Actuator Options:
If, at any time, the position of the motor actuator valve is unknown (i.e., at first power up), the valve will
be reset to the HOME position by activating the HOME output for 10 seconds.
NOTE
!