Function 1: Read Coil
Function 3: Holding Register
Function 6: Write Single Register
Read the current state of the contact (energized or de-energized). Maximum address length of the query is 8.
The Value 1 = ON (Relay Energized)
The Value 0 = OFF
Example using default configuration
Address
Value Range
Note
00001
0 – OFF 1 - ON
Relay 1 Status
00002
0 – OFF 1 - ON
Relay 2 Status
00003
0 – OFF 1 - ON
Relay 3 Status
00004
0 – OFF 1 - ON
Relay 4 Status
00005
0 – OFF 1 - ON
Relay 5 Status
00006
0 – OFF 1 - ON
Relay 6 Status
00007
0 – OFF 1 - ON
Relay 7 Status
00008
0 – OFF 1 - ON
Relay 8 Status
Read current configuration of contact control mode.
0 - AUTO: The relay turns ON/OFF according to the status of the linked Input Sensor.
1 - OFF: The relay has been manually set to OFF.
2 - ON: The relay has been manually set to ON.
Example using default configuration
Address
Value Range
Note
40001
0 – Auto 1 – OFF 2 - ON
Read Control Mode
40002
0 – Auto 1 – OFF 2 - ON
Read Control Mode
40003
0 – Auto 1 – OFF 2 - ON
Read Control Mode
40004
0 – Auto 1 – OFF 2 - ON
Read Control Mode
40005
0 – Auto 1 – OFF 2 - ON
Read Control Mode
40006
0 – Auto 1 – OFF 2 - ON
Read Control Mode
40007
0 – Auto 1 – OFF 2 - ON
Read Control Mode
40008
0 – Auto 1 – OFF 2 - ON
Read Control Mode
Use this function to turn ON or OFF a single relay. Also it allows you to set the relay to be control by the linked
Input Sensor.
0 - AUTO: The relay turns on/off according to the linked Input Sensor states.
1 - OFF: The relay has been manually set to OFF.
2 - ON: The relay has been manually set to ON.
Example using default configuration
Address
Value Range
Note
40001
0 – Auto 1 – OFF 2 - ON
Set Control Mode
40002
0 – Auto 1 – OFF 2 - ON
Set Control Mode
40003
0 – Auto 1 – OFF 2 - ON
Set Control Mode
40004
0 – Auto 1 – OFF 2 - ON
Set Control Mode
40005
0 – Auto 1 – OFF 2 - ON
Set Control Mode
40006
0 – Auto 1 – OFF 2 - ON
Set Control Mode
40007
0 – Auto 1 – OFF 2 - ON
Set Control Mode
40008
0 – Auto 1 – OFF 2 - ON
Set Control Mode
Device Configuration
27