Power
Voltage Rating
24VAC, 50/60Hz; 24VDC
Current Rating
600mA max.
Wired Inputs
Digital
Two (2) 24V, 10mA max. per channel
Wired Outputs
Relay
Four (4) Dry Contact, Form C, 1A @ 24VDC resistive, 0.5A
@ 120VC
Communications Ports
Ethernet
10/100 BASE-T, RJ45 connector; 500VAC RMS isolation
EIA-232
DB9 female connector; 9600 baud; No parity, 8 data bits,
1 stop bit
EIA-485
1200, 2400, 9600 or 19200 baud (selectable); Parity: none,
even or odd, 8 data bits, 1 stop bit
Protocols
TCP/IP, HTML, TFTP, SNMP
V1: V2C MIB-2 compliant; NMS Manageable with Get
Modbus (EIA-485)
Modbus Slave; RTU mode; Supports function codes 03
Modus TCP/IP UDP/IP
Modbus Slave; TCP/IP transmission protocol
BACnet/IP
ASHRAE STD 135-2004 Annex J
BACnet MS/TP
EIA-485
Terminal Emulation
VT100 compatible
Login Security
Web Browser Access (Ethernet)
1 Web password Read Only; 1 Web password Read/Write
Terminal Emulation Access
None
Table C.1