rletech.com
Wi-MGR User Guide
31
3
Web Interface
All fields in the following table will not be available for each sensor. Only the configurable
options that apply to each sensor are displayed in that sensor’s configuration menu. Editable
options are as follows:
Option
Description
Model
To edit the sensor model, select the type of sensor from the drop-
down list by clicking on the down arrow.
This number is used by the Wi-MGR to identify what kind of sensor
is being read in to the system. The possible values are:
Wi-TS
54
Wi_THS
48
Wi-DIT
61
Wi-ASx/Wi-MS
41
Wi-TH2
52
Counter
11
BAPI
76
Wi-LD
76
Thermistor
57
SetPointOverride
5B
Wi-TC9
74
Id
Uneditable; this reflects the value currently saved as the model
number.
Out of Service
A binary number used to determine if a sensor is online or offline.
0 = online, any other non-zero number = offline
Serial #
This is the unique number broadcasted from the sensor to the
Wi-MGR for identification. Each sensor has a unique serial number.
The Serial # field should automatically fill when the Wi-MGR
automatically discovers the sensors.
If a serial number is not automatically updated and needs to be
entered manually, the serial number should be entered from left to
right. Point Six sensors have two serial numbers on the sensors,
one that reads from left to right and one that reads from right to left.
The serial number should be entered starting with a number (not
zero) or an alpha character.
Enter the appropriate serial number, listed on the bottom of the
sensor, in the provided text field.
Raw Data #1, #2, #3
Uneditable; this is the uncalculated data received from the wireless
sensor. This data is then processed by the Wi-MGR to a calculated
value.
Converted Data #1,
#2, #3
Uneditable; this is the calculated data processed from the raw data.
This data is then displayed by the Wi-MGR and used for Modbus,
BACnet, and SNMP output.
Sensor Reading Age
Uneditable; the amount of time that has passed, in seconds, since
the Wi-MGR has received a broadcast signal from this sensor.
Table 3.3
Wireless Sensor Configuration Options
Содержание Falcon Wi-MGR
Страница 1: ...Monitoring User Guide Wi MGR Wireless Sensor Network Manager Version 1 8 Firmware Version 6 3 17...
Страница 8: ...8 Wi MGR User Guide 800 518 1519 B Troubleshooting 69 C Technical Specifications 73...
Страница 10: ...10 Wi MGR User Guide 800 518 1519...
Страница 68: ...68 Wi MGR User Guide 800 518 1519...