Wi-MGR User Guide
43
3
Web Interface
Option
Description
Digital IO
Enable or disable the digital inputs and relay outputs. If there are no
digital inputs and relay outputs installed on your Wi-MGR, select
Not Installed.
Default: Enabled
Digital Inputs #1, #2, #3, and #4
Each digital input has its own configurable options, but all fields have several read-only
values that are displayed. These fields include the input’s modbus register number, the
input’s bacnet instance, and the input’s status information.
Adjust the following editable fields as necessary:
Input Type
Decide if the point should go into alarm or simply report its status.
Default: Alarm
Polarity
Note the polarity of the input, normal or reversed.
Default: Normal
Active Text
This text will appear on the Wi-MGR’s home page when the input
goes into an alarm condition.
Default: #a, where # represents the digital input number
Inactive Text
This text will appear on the Wi-MGR’s home page when the input is
in its normal operating condition.
Default: #i, where # represents the digital input number
Alarm Delay
The number of seconds that passes between the time the point
goes into an alarm state and the time that alarm is annunciated.
Default: 0
Active Relay
Designate which relay outputs are activated when the point goes
into alarm.
Select: None, K1, K2, or K1+K2
Default: None
Table 3.5
Digital IO Configuration Options