19
Beacon 110 Rig Monitor Operator’s Manual
Alarm Indications
NOTE:
The Beacon 110 Rig Monitor includes alarm on and alarm off delay settings for alarm 1
and alarm 2. The alarm indications described in this section operate according to the
factory set alarm settings. See Table 6 on page 23 for all the factory settings.
NOTE:
You can select normally energized (N. EN) or normally de-energized (N. DE-EN)
alarm 1 and alarm 2 relay action settings in Configuration Mode. The following
sections describe the standard factory setting for these relays which is N. DE-EN.
The fail relay is set as normally energized in the firmware and is not user-adjustable.
CAUTION:
Changing the relay action setting for the Alarm 1 relay in Configuration Mode will
cause the strobe/horn to be on during normal operation.
Table 5: Visual and Audible Alarm Indications
Condition
Cause
Visual Indication(s)
Audible
Indication
Alarm 1
1
Increasing gas reading at or above the
alarm 1 setpoint
• Alarm 1 LED is on
• Gas reading alternates with
ALARM-1
message
• Strobe/horn turns on
• Pulsing tone
• Strobe/horn
turns on
Alarm 2
1
Increasing gas reading at or above the
alarm 2 setpoint
• Alarm 2 LED is on
• Gas reading alternates with
ALARM-2
message
• Pulsing tone
Fail
• Disconnected or misconnected
detector head wiring
• Display reading at -10% of full scale
or lower
• Defective components
• Fail LED is on
•
FAIL
message replaces gas
reading
NOTE: There is a 30 second
delay on the fail indications.
• Steady tone
Low Power
Dead 12 VDC battery
• Fail LED is on
•
LowPower
message
• None
NOTE: Under typical operating conditions, there will be no low power alarm. The 12 VDC battery that is rec
-
ommended for operation will die before the power converter recognizes a low power condition.
*
1
If the Beacon 110 Rig Monitor is in both an alarm 1 and an alarm 2 condition, both alarm LEDs are on
and the display alternates between the gas reading and the ALMS 1&2 message.