Beacon 110 Rig Monitor Operator’s Manual
22
Chapter 5: Configuration Mode
Overview
This chapter describes how to view and change Beacon 110 Rig Monitor parameters using
Configuration Mode. It is accessed using the program buttons.
Configuration Mode includes a 5-minute time-out feature. If you do not press a control button for 5
minutes, the Rig Monitor automatically returns to normal operation.
NOTE:
If the Beacon 110 Rig Monitor returns to normal operation because of a time-out, it
enters a warm-up period just as it does when it is first turned on.
If you are installing a new Rig Monitor, it has been set up at the factory. Use
Configuration Mode only if you want to change the Rig Monitor’s setup.
Viewing & Changing Beacon 110 Rig
Monitor Parameters
1. While in normal operation, simultaneously press and hold the UP/YES and ENTER buttons for
5 seconds to enter Configuration Mode. Release the buttons when the following screen
appears.
2. If you want to exit Configuration Mode, press and release the DOWN/NO button and the Rig
Monitor will return to normal operation.
If you want to continue in Configuration Mode, press and release the UP/YES button. The
target gas and the full scale will be displayed for a few seconds before the first adjustable
parameter, the alarm 1 setpoint, is displayed.
3. If you want to change the currently displayed parameter, use the UP/YES and DOWN/NO
buttons to adjust it to the desired setting, then press ENTER to continue to the next parameter.
If the currently displayed parameter is OK, press the ENTER button to proceed to the next
parameter.
Table 6 lists the Rig Monitor parameters you can set. Table 6 also lists the factory set
value for each parameter.
Enter
Config?