28
•
Chapter 4: Operation
65-2670XL-XX-07 M2A-XL Transmitter
Alarm 1 Condition
Alarm 1 Condition Indications
When the gas reading reaches the alarm 1 setpoint, the M2A-XL senses an alarm 1 condition. The
M2A-XL alerts you to an alarm 1 condition as follows:
• The A1 LED turns on.
• The gas reading alternates with the
ALARM-1
message.
• The alarm 1 relay energizes.
Responding to an Alarm 1 Condition
1. Follow your established procedure for a low level toxic gas condition.
2. After the gas reading falls below the alarm 1 setpoint, press the ENTER button to reset the
alarm 1 circuit. Resetting the alarm 1 circuit turns off the A1 LED, resets the OLED display,
and de-energizes the alarm 1 relay.
NOTE:
If the ENTER button is pressed while the M2A-XL is in an alarm 1
condition, the A1 LED will flash but all other indications will remain
unchanged.
You cannot de-energize the alarm 1 relay until the gas reading falls below
the alarm 1 setpoint.
Alarm 2 Condition
Alarm 2 Condition Indications
When the gas reading reaches the alarm 2 setpoint, the M2A-XL senses an alarm 2 condition. The
M2A-XL alerts you to an alarm 2 condition as follows:
• The A2 LED turns on.
• The gas reading alternates with the
ALARM-2
message.
• The alarm 2 relay energizes.
NOTE:
If the M2A-XL is in both an alarm 1 and alarm 2 condition, both the A1 and A2 LEDs
will be on, the gas reading will alternate with the
ALMS 1&2
message, and both alarm
relays will energize
.