65-2670XL-XX-07 M2A-XL Transmitter
Chapter 1: Introduction
•
7
Specifications
Table 1 lists specifications for the M2A-XL.
Table 1: M2A-XL Specifications
Target Gas/Detection
Range
• Ammonia (NH
3
): 0 - 75.0 ppm, 0.1 ppm increments
• Ammonia (NH
3
): 0 - 100 ppm, 1 ppm increments
• Ammonia (NH
3
): 0 - 200 ppm, 1 ppm increments
• Ammonia (NH
3
): 0 - 500 ppm, 1 ppm increments
• Chlorine (Cl
2
): 0 - 3.00 ppm, 0.01 ppm increments
• Chlorine (Cl
2
): 0 - 5.00 ppm, 0.01 ppm increments
• Chlorine (Cl
2
): 0 - 10.0 ppm, 0.1 ppm increments
• Chlorine Dioxide (ClO
2
): 0 - 1.00 ppm, 0.01 ppm increments
• Chlorine Dioxide (ClO
2
): 0 - 3.00 ppm, 0.01 ppm increments
• Chlorine Dioxide (ClO
2
): 0 - 5.00 ppm, 0.01 ppm increments
• Hydrogen Cyanide (HCN): 0 - 15.0 ppm, 0.01 ppm increments
• Sulfur Dioxide (SO
2
): 0 - 10.0 ppm, 0.01 ppm increments
Alarm Settings
(Alarm 1/Alarm 2)*
• Ammonia (0 - 75.0 ppm and 0 - 100 ppm): 12 ppm / 25 ppm
• Ammonia (0 - 200 ppm): 25 ppm / 35 ppm
• Ammonia (0 - 500 ppm): 35 ppm / 300 ppm
• Chlorine (0 - 3.00 ppm): 0.50 ppm / 1.00 ppm
• Chlorine (0 - 5.00 ppm): 0.50 ppm / 1.50 ppm
• Chlorine (0 - 10.0 ppm): 1.0 ppm / 3.0 ppm
• Chlorine Dioxide (0 - 1.00 ppm): 0.10 ppm / 0.30 ppm
• Chlorine Dioxide (0 - 3.00 ppm): 0.30 ppm / 1.00 ppm
• Chlorine Dioxide (0 - 5.00 ppm): 0.50 ppm / 1.00 ppm
• Hydrogen Cyanide (0 - 15.0 ppm): 5.0 ppm / 10.0 ppm
• Sulfur Dioxide (0 - 10.0 ppm): 1.0 ppm / 2.0 ppm
Sampling Method
Diffusion
Flow Rate for
Calibration
0.25 LPM (using a 0.5 LPM regulator that is normally recommended
for M2A-XLs will result in an inaccurate calibration)
Input Power
10 - 30 VDC
Controls
• Three push button switches
• Three magnetic switches for non-intrusive calibration
Weight
5.5 lbs.
Signal Output
4 to 20 mA with impedance maximums listed below
• -12 VDC: 500 ohms impedance max
• -24 VDC: 1000 ohms impedance max
RS-485 Modbus