Technical Informations
UPS-Manual
26
EN
Model
1KVA
2KVA
3KVA
(Bypass Mode)
<105% continuous
>106% ~ 120% for 250 seconds shuts down
>
121% ~ 130% for 125 seconds shuts down
>131% ~ 135% for 50 seconds shuts down
>136% ~ 145% for 20 seconds shuts down
>146% ~ 148% for 5 seconds shuts down
>149% ~ 157% for 2 seconds shuts down
>158% ~ 176% for 1 seconds shuts down
>177% ~ 187% for 0,32 seconds shuts down
>188% for 0,16 seconds shuts down
Buzzer continuously alarms.
Short Circuit
Bypass mode : Input Fuse/Input Breaker
Normal Mode: Output Breaker/Electronic Circuit
Battery Mode: Output Breaker/Electronic Circuit
Battery
ABDM
EPO
UPS shuts down immediately
Normal Mode
Transfer to Bypass Mode
Over
Temperature
Battery Mode
UPS shuts down immediately
Audible Alarm
Battery Mode
Sounding once every 1,5 seconds
Low Battery
Sounding once every 0,2 seconds
Overload
Sounding once every 3 second
Fault
Continuously Sounding (or Sounding once every 3 second)
Physical
Dimensions(HxWxD in mm)
88(2U)x440x405
88(2U)x440x 650
88.8(2U)x440x 650
Weights
15,7kg (34,5Ib)
29,4kg (64,7Ib)
29,7kg (65,3Ib)
Input Connection
10A, IEC 320-C14
10A, IEC 320-C14
16A, IEC 320-C20
Output Connection
230V
(6) 10A,IEC 320-C13
(4) 10A,IEC 320-C13
(1) 16A,IEC 320-C19
Environmental
Operation Temperature
0 - 40 °C
Noise Level
< 50 dBA
Relative Humidity
0 to 90% (Without condensation)
Interface
Interface Type
1 *USB port+ 1*RS-232 port
SNMP
Power management from SNMP manager and Web browser
Compatible platforms
Windows 95/98/NT/2000/XP/Vista, Novell NetWare, Linux, etc.
Standards and Certification
Safety
IEC/EN 62040-1-1,IEC 60950-1
Performance
IEC/EN 62040-3
EMC
IEC/EN62040-2 Class A, FCC Part 15 Subpart B Class A, IEC/EN55011, CISPR11,
IEC61000-4-2/-3/-4/-5, IEC61000-2-2, IEC61000-3-2/-3
Markings
CE
Содержание PMC 12