background image

Important Safety Instruction

UPS-Manual

4

EN

1.  Important Safety Instruction

1.1.  Documentation Notes

The  audience  for  this  guide  is  the  technical
specialists  familiar  with  the  assembly,  installa-
tion and operation of the PMC12 UPS-System.
You  should  read  this  operating  guide  prior  to
the  commissioning  and  store  the  guide  so  it  is
readily accessible for subsequent use.
Rittal  cannot  accept  any  liability  for  damage
and  operational  malfunctions  that  result  from
the nonobservance of this guide.

1.2.  Retention of the Documents

This  guide  and  all  associated  documents  are
part  of  the  product.  They  must  be  given  to  the
operator of the unit and must be stored so they
are available when needed.

1.3.  Used Symbols

The  following  safety  and  other  notes  are  used
in this guide:

Symbol for a handling instruction:

  This  bullet  point  indicates  that  you  should

perform an action.

Safety and other notes:

Danger!

Immediate  danger  to  health  and
life!

Warning!

Possible  danger  for  the  product
and the environment!

Note!

Useful  information  and  special
features.

1.4.  An Important Notice

1.  Assembly and installation of the UPS, in

particular  for  wiring  the  enclosures  with
mains power, may be performed only by
a  trained  electrician.  Other  tasks  asso-
ciated  with  the  UPS,  such  as  the  as-
sembly  and  installation  of  system  com-
ponents  with  tested  standard  connec-
tors,  and  the  operation  and  configura-
tion of the PMC12 UPS-System may be
performed only by instructed personnel.

2.  Do  not  open  the  case,  as  there  are  no

serviceable  parts  inside.  Your Warranty
will be void.

3.  Do  not  try  to  repair  the  unit  yourself;

contact  your  local  supplier  or  your  war-
ranty will be void.

4.  If  liquids  are  split  onto  the  UPS  or  for-

eign  objects  dropped  into  the  unit,  the
warranty will be null and void.

5.  Do  not  install  the  UPS  in  an  environ-

ment with sparks, smoke or gas.

6.  This UPS is equipped with an EMI filter.

To  prevent  potential  leakage  current
hazard, ensure that the AC main supply
is securely grounded.

7.  This  UPS  is  designed  to  be  installed

and  commissioned  in  a  sheltered,  con-
trolled environment as follows:

Operating  temperature  0-40°C
and  30-90%  non-condensing
humidity.

Always  avoid  contact  with  direct
sunlight.

Installing  the  UPS  in  inflamma-
ble or hazardous environment.

Dusty,  corrosive  and  salty  envi-
ronments can do damage to any
UPS.

Install  the  UPS  indoors  as  it  is
not  designed for  installation  out-
doors.

8.  To prevent any overheating of the UPS,

keep  all  ventilation  openings  free  from
obstruction,  and  do  not  place  anything
on  top  of  the  UPS.  Keep  the  UPS  rear
panel 20 cm away from the wall or other
obstructions.

9.  The battery will discharge naturally if the

system is unused for any length of time.

10. Install  the  UPS  away  from  objects  that

give  off  excessive  heat  and  areas  that
are excessively wet.

11. Always  switch  off  the  UPS  and  discon-

nect  the  batteries  when  relocating  the
UPS.

12. It  should  be  recharged  every  2-3

months  if  unused.  If  this  is  not  done,
then  the  warranty  will  be  null  and  void.
When  installed  and  being  used,  the
batteries will be automatically recharged
and kept in top condition.

13. Make  sure  that  the  AC  Utility  outlet  is

correctly grounded.

14. Please  ensure  that  the  input  voltage  of

the UPS matches the utility supply volt-
age.  Use  a  certified  input  power  cable
with  the  correct  plugs  and  sockets  for
the appropriate voltage system.

Содержание PMC 12

Страница 1: ...nversion true online UPS System 1 3kVA FRIDHELM LOH GROUP R i t t a l GmbH Co KG Auf dem Stützelberg D 3 5 7 4 5 H e r b o r n Deutschland Germany Email Info rittal de http www rittal com Service Tel 49 0 2772 505 0 Service Fax 49 0 2772 505 2319 A 38333 03 IT 74e doc ...

Страница 2: ...Important Safety Instruction UPS Manual 2 EN Microsoft Windows is a registered trademark of Microsoft Corporation Acrobat Reader is a registered trademark of Adobe Systems Incorporated ...

Страница 3: ...uration Setup 12 4 4 OPERATION 13 4 4 1 Start Up In Normal Mode 13 4 4 2 Start up in Battery Mode Cold Start 13 4 4 3 Check Measured Values Figures detected by UPS 14 4 4 4 UPS Default Data and Special Function Execution 14 4 4 5 UPS Default Settings and Their Alternatives 16 4 4 6 UPS Is Off Due to Unknown Reason and Its Trouble Shooting 16 4 4 7 Shut Off 17 4 5 STATUS ALARM BUZZER 17 4 6 BATTERY...

Страница 4: ...the unit yourself contact your local supplier or your war ranty will be void 4 If liquids are split onto the UPS or for eign objects dropped into the unit the warranty will be null and void 5 Do not install the UPS in an environ ment with sparks smoke or gas 6 This UPS is equipped with an EMI filter To prevent potential leakage current hazard ensure that the AC main supply is securely grounded 7 T...

Страница 5: ...d safety regulations 16 Use only genuine or recommended parts and accessories see Chapter 4 The use of other parts can void the li ability for any resulting consequences 1 5 Storage Instruction For extended storage in moderate climate the batteries should be charged for 12 hours every 3 months interval by connecting the UPS to the utility supply and switch on input breaker lo cated at UPS rear pan...

Страница 6: ...raints 1 This UPS is equipped with fully digitalized control logic for greater functionality and enhanced high level of power protection Digital signal processing DSP also pro vides the UPS with powerful communica tion capability which enhances the flexibil ity for easy remote control and monitoring 2 Wide input voltage tolerance from 184V 288V allows under voltage or over voltage correction witho...

Страница 7: ... Switch Special functions log in out Go to next page Go to previous page or change the setting of the UPS To re confirm the change of UPS Setting 3 1 1 Symbols on the LCD Display Panel Item Symbol Description 1 LINE Utility or Bypass Source 2 Battery Low 3 Battery Abnormal 4 UPS Overloading 5 Site Wiring Fault 6 UPS Working in Service Mode 7 OFF UPS Shutoff 8 FAIL UPS Abnormal Lock 9 UPS Flow Char...

Страница 8: ...32 Port 3 Emergency Power Off EPO Dry Contact Signal inputs 4 Communication Card Options Slot 5 External Battery Connector 6 AC power connection socket 7 AC Outlets 8 Two programmable outlets 9 Utility Input fuse holder 10 Cooling Fans 11 Output fuse holders 12 Output fuse holders for two programmable outlets ...

Страница 9: ...Sensitivity High 220V System 184V 260V 194V 260V Note CF50 CF60 Frequency Converter mode 50 to 60Hz or vice versa Sensitivity Low 184 260V High 194 260V 3 3 2 Programmable Outlet Setting The UPS is equipped with 2 programmable outlets for use to supply to less critical loads These outlets can be disabled to shed the less critical loads during back up modes or overload conditions to maintain qualit...

Страница 10: ...tware of the UPS is compatible with many operating systems such as Windows 98 2000 ME NT XP and Vista For other applications such as Novell NetWare Unix Li nux please contact your local dealer for suit able software All the communication ports including optional cards can be active use simultaneously to monitor the UPS status However only 1 com munication interface at any one time with the highest...

Страница 11: ...S communication software with RS232 and USB cable 1 set of Tower Rack Accessories Kit 4 2 Selecting Installation Position Warning The UPS is heavy Select a location sturdy enough to handle the UPS weight To ensure proper operation and long operating life always position the UPS according to the following requirement 1 Keep minimum 20cm 8 inches distance clearance from the rear panel of the UPS to ...

Страница 12: ...Installation and Operation UPS Manual 12 EN 4 3 2 Power Module Battery Module Step 1 Step 2 4 3 3 Rack Mount Configuration Setup Step 1 Step 2 Step 3 Step 4 ...

Страница 13: ...ng C 5 In case of failure in self test the LCD display will illustrate as drawing D then an error code or error status will be shown on the screen drawing D drawing E 6 Your start up operation of the UPS is com pletely now as illustrated as drawing E Make sure the UPS is plugged onto the wall receptacle for charging at least 8 hours and the batteries of the UPS are fully charged 4 4 2 Start up in ...

Страница 14: ... will illustrate in se quence from drawing E Input Voltage drawing J Input Frequency drawing K UPS Output Voltage drawing L UPS Output Fre quency drawing M UPS Output Load per centage drawing N UPS Battery Voltage drawing O UPS inner temperature drawing J drawing K drawing L drawing M drawing N drawing O 4 4 4 UPS Default Data and Special Function Execution 1 After UPS is turned on successfully us...

Страница 15: ...y will show in sequence drawing P1 buzzer drawing Q1 self test drawing R1 Bypass Voltage drawing S Output Fre quency Synchronized Window drawing T Inverter Output Voltage drawing U1 UPS Operation Mode drawing V Output Voltage Fine Tuning drawing Q1 drawing Q2 drawing R1 drawing R2 drawing S drawing T drawing U1 drawing U2 drawing U3 drawing V ...

Страница 16: ... Output Voltage of which voltage is 220V 230V or 240V for 220V AC system 6 Drawing U1 U2 and U3 mean the operation modes of the UPS of which alternative is Online fixed 50Hz Output or fixed 60Hz Output 7 Drawing V means the adjustments of the Inverter Output which may be calibrated as 0 1 1 2 2 3 or 3 8 When all the setting changes are done you have to press enter key pad to save all the changes w...

Страница 17: ...of the common UPS statuses with respect to their buzzer beep descriptions 4 6 Battery Replacement Step 1 Step 2 Step 3 Status Definitions Buzzer Beep Descriptions UPS faulty Inverter shutdown All functions inhabited Long Continuous Beep UPS faulty loads continue to be supplied via Inverter or Bypass Single successive beep with 2 sec interval battery mode Single short successive beep with 1 sec int...

Страница 18: ...nvert DC to AC and supply to loads with clean stable power LEDs remain illuminated Mains Absent under or over voltage Rectifier and charger stop operating Battery discharge via DC DC boost circuit and supply to Inverter Loads continue to receive supply from Inverter Alarm buzzer beeps UPS now on battery mode LED Nr 2 off Mains Absent Battery low voltage Rectifier and charger stop operating Battery...

Страница 19: ...ly modern day electronics IT equipment generate an inrush current when switching on The amount of inrush current varies from equipment to equipment some can be as high as 6 times its rated capacity while others produce negligible inrush To prevent severe damage to its Inverter cause by the inrush produce by the loads the UPS is equipped with electronics overload protec tion feature as standard If ...

Страница 20: ... the problem persists please contact your local dealer for assistance Situation Check Items Solution UPS Fault LED Read the error code from the LCD display 1 Er05 Er25 2 Overload 3 Er11 UPS Over Temperature 4 Site wiring Ground fault 5 Er14 Fans out of order 6 Other error codes 1 Check battery connection if is properly done Measure Battery voltage to ensure batteries are charged or healthy Recharg...

Страница 21: ...wer source Check that the battery connectors are fully engaged Allow the battery to recharge if the batter is weak If problem persist after recharging replace the battery If problem persist consult your local dealer Rittal or customer service for technical assistance Note When the Fault LED is illuminated the error code is shown in the LCD display Check the error code 6 2 Error Codes and Their Des...

Страница 22: ... whole parallel system or specific values from the single modules 8 1 SNMP Adapter The adapter may be configured via Telnet HTTP Web Browser or serial connection Terminal For normal operation at least one network connection Ethernet is required The SNMP adapter can be used utilising the RCCMD send function for an automatic net work wide shut down or just for informing con nected users The shut dow...

Страница 23: ... PMC Software Our SNMP Interfaces are compatible to RCCMD 9 Customer Service If you have any technical questions or ques tions concerning our product spectrum contact the following service address Tel 49 0 2772 505 1855 http www rimatrix5 com E mail info rittal de ...

Страница 24: ...ge High Line Comeback 230V 278Vac Frequency 50 60 Hz auto select 5Hz Phase Single phase with ground PF 0 99 at full ratedlinearload Typical Transfer Time 0ms AC Leakage current 230V 3 5mA Surge Protection 230V 300 joules Output Voltage 230V 230V adjustable to 220 230 240 Voltage Regulation 1 until low battery warning Frequency Synchroniz ed Range 3Hz or 1Hz setting by software Frequency Battery Mo...

Страница 25: ... Sealed non spillage maintenance free lead acid Transfer Time AC to DC Zero Inverter to Bypass 2 5ms Typical Zero DC Start Yes Self Diagnostics By button of the panel or Software Control Front Panel LED Load Level Battery Level Battery Mode Normal Mode Bypass Mode Self Test Weak Bad Battery Site Wiring Fault Fault Overload Programmable Outlet1 Programmable Outlet2 Key ON Button OFF Button Test Ala...

Страница 26: ...ry 1 5 seconds Low Battery Sounding once every 0 2 seconds Overload Sounding once every 3 second Fault Continuously Sounding or Sounding once every 3 second Physical Dimensions HxWxD in mm 88 2U x440x405 88 2U x440x 650 88 8 2U x440x 650 Weights 15 7kg 34 5Ib 29 4kg 64 7Ib 29 7kg 65 3Ib Input Connection 10A IEC 320 C14 10A IEC 320 C14 16A IEC 320 C20 Output Connection 230V 6 10A IEC 320 C13 4 10A ...

Страница 27: ...Module Load 100 66min 34min 30min 80 90min 52min 46min 60 120min 69min 60min 40 180min 109min 95min 1 extended Battery module 20 350min 210min 180min Load 100 130min 66min 60min 80 160min 90min 75min 60 220min 160min 109min 40 325min 180min 160min 2 extended Battery module 20 630min 350min 310min ...

Страница 28: ...Technical Informations UPS Manual 28 EN ...

Отзывы: